63230-300-212

Appendix A—Abbreviated Register Listing

April 2001

Register Listing

 

 

Table A–3:Abbreviated Register List

Register

Description

Scale

Units

Register Range

Number

Factor

 

 

 

 

 

 

 

 

1649

Maximum Voltage Fundamental Coincident Angle, C-N/C-A

0.1 °

0 to 3,599

 

 

 

 

 

1650

Maximum Voltage Fundamental RMS Magnitude, N-G

E

Volts/Scale

0 to 32,767

 

 

 

 

 

1651

Maximum Voltage Fund. Coincident Angle, N-G

0.1 °

0 to 3,599 ￿

 

 

 

 

 

1655

Maximum Fundamental Real Power, Phase A

F

kW/Scale

-32,767 to ￿32,767

 

 

 

 

 

1656

Maximum Fundamental Real Power, Phase B

F

kW/Scale

-32,767 to 32,767

 

 

 

 

 

1657

Maximum Fundamental Real Power, Phase C

F

kW/Scale

-32,767 to 32,767

 

 

 

 

 

1658

Maximum Fundamental Real Power, Total

F

kW/Scale

-32,767 to 32,767

 

 

 

 

 

1659

Maximum Fundamental Reactive Power, Phase A

F

kVA/Scale

-32,767 to 32,767

 

 

 

 

 

1660

Maximum Fundamental Reactive Power, Phase B

F

kVA/Scale

-32,767 to 32,767

 

 

 

 

 

1661

Maximum Fundamental Reactive Power, Phase C

F

kVA/Scale

-32,767 to 32,767

 

 

 

 

 

1662

Maximum Fundamental Reactive Power, Total

F

kVA/Scale

-32,767 to 32,767

 

 

 

 

 

1664

Maximum Distortion Power, Phase A

F

kW/Scale

-32,767 to 32,767

 

 

 

 

 

1665

Maximum Distortion Power, Phase B

F

kW/Scale

-32,767 to 32,767

 

 

 

 

 

1666

Maximum Distortion Power, Phase C

F

kW/Scale

-32,767 to 32,767 ￿

 

 

 

 

 

1667

Maximum Distortion Power, Total

F

kW/Scale

-32,767 to 32,767

 

 

 

 

 

1668

Maximum Distortion Factor, Phase A

F

0.10

0 to 1,000

 

 

 

 

 

1669

Maximum Distortion Factor, Phase B

F

0.10

0 to 1,000

 

 

 

 

 

1670

Maximum Distortion Factor, Phase C

F

0.10

0 to 1,000 ￿

 

 

 

 

 

1671

Maximum Distortion Factor, Total

F

0.10

0 to 1,000

 

 

 

 

 

1674

Maximum Harmonic Current, Phase A

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1675

Maximum Harmonic Current, Phase B

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1676

Maximum Harmonic Current, Phase C

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1677

Maximum Harmonic Current, Neutral

B

Amps/Scale

0 to 32,767

 

 

 

 

 

1678

Maximum Harmonic Voltage, A-N

D

Volts/Scale

0 to 32,767

 

 

 

 

 

1679

Maximum Harmonic Voltage, B-N

D

Volts/Scale

0 to 32,767

 

 

 

 

 

1680

Maximum Harmonic Voltage, C-N

D

Volts/Scale

0 to 32,767 ￿

 

 

 

 

 

1681

Maximum Total Demand Distortion

0.01

0 to 10,000

 

 

 

 

 

1684

Maximum Current, Positive Sequence, Magnitude

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1685

Maximum Current, Positive Sequence, Angle

0.1

0 to 3,599

 

 

 

 

 

1686

Maximum Current, Negative Sequence, Magnitude

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1687

Maximum Current, Negative Sequence, Angle

0.1

0 to 3,599

 

 

 

 

 

1688

Maximum Current, Zero Sequence, Magnitude

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1689

Maximum Current, Zero Sequence, Angle

0.1

0 to 3,599

 

 

 

 

 

1690

Maximum Voltage, Positive Sequence, Magnitude

D

Volts/Scale

0 to 32,767

 

 

 

 

 

1691

Maximum Voltage, Positive Sequence, Angle

0.1

0 to 3,599

 

 

 

 

 

1692

Maximum Voltage, Negative Sequence, Magnitude

D

Volts/Scale

0 to 32,767

 

 

 

 

 

See “How Power Factor is Stored in the Register” on page 128.

The alternate storage method for power factor (PF) is useful for outputting PF on analog outputs. The PF value is stored as a positive value between 0 and 2, centered around 1 (unity). A value of 0 lagging maps to 0; -0.999 maps to 0.999;0.999 leading maps to 1.001; and 0 leading maps to 2. The alternate PF is also stored with a scale factor 0.001.

These configuration registers require that you enter the setup mode to change the register’s contents. Issue command 9020 to enter setup mode and 9021 to exit setup mode. See “Using the Command Interface to Change Configuration Registers” on page 187 for instructions on

￿how to use the setup-mode commands.

Quantity available for 4-wire system only. Value set to -32,768 if not available.