Appendix A—Abbreviated Register Listing

63230-300-212

Register Listing

April 2001

 

 

Table A–3:Abbreviated Register List

Register

Description

Scale

Units

Register Range

Number

Factor

 

 

 

 

 

 

 

 

 

 

 

 

Discrete Input Point Assignment to Discrete Input Status

 

 

 

 

 

Bitmap Bit 11

 

 

 

3361

 

IO Point Number for Discrete Input to include in Discrete Input

0 to 66

 

 

Status Bitmap: Bit 11.

 

 

 

 

 

0 = none, default = 38 (Dig In C4)

 

 

 

 

 

 

 

 

 

 

 

Discrete Input Point Assignment to Discrete Input Status

 

 

 

 

 

Bitmap Bit 12

 

 

 

3362

 

IO Point Number for Discrete Input to include in Discrete Input

0 to 66

 

 

Status Bitmap: Bit 12.

 

 

 

 

 

0 = none, default = 39 (Dig In C5)

 

 

 

 

 

 

 

 

 

 

 

Discrete Input Point Assignment to Discrete Input Status

 

 

 

 

 

Bitmap Bit 13

 

 

 

3363

 

IO Point Number for Discrete Input to include in Discrete Input

0 to 66

 

 

Status Bitmap: Bit 13.

 

 

 

 

 

0 = none, default = 40 (Dig In C6)

 

 

 

 

 

 

 

 

 

 

 

Discrete Input Point Assignment to Discrete Input Status

 

 

 

 

 

Bitmap Bit 14

 

 

 

3364

 

IO Point Number for Discrete Input to include in Discrete Input

0 to 66

 

 

Status Bitmap: Bit 14.

 

 

 

 

 

0 = none, default = 41 (Dig In C7)

 

 

 

 

 

 

 

 

 

 

 

Discrete Input Point Assignment to Discrete Input Status

 

 

 

 

 

Bitmap Bit 15

 

 

 

3365

 

IO Point Number for Discrete Input to include in Discrete Input

0 to 66

 

 

Status Bitmap: Bit 15.

 

 

 

 

 

0 = none, default = 42 (Dig In C8)

 

 

 

 

 

 

 

 

 

Communication

 

 

 

 

 

 

 

 

 

 

 

 

RS-485 Comm Port #1 Operation Mode

 

 

 

3400

 

0

= Modbus Slave (default)

0 to 1

 

 

1

= Jbus Slave

 

 

 

 

 

 

 

 

 

 

 

RS-485 Comm Port #1 Address

 

 

 

3401

 

Valid Addresses: (Default = 1)

0 to 255

 

Modbus: 0 to 247

 

 

 

 

 

 

 

Jbus: 0 to 255

 

 

 

 

 

 

 

 

 

 

 

RS-485 Comm Port #1 Baud Rate

 

 

 

 

 

0

= 1200

 

 

 

 

 

1

= 2400

 

 

 

3402

 

2

= 4800

0 to 5

 

 

3

= 9600 (default)

 

 

 

 

 

4

= 19200

 

 

 

 

 

5

= 38400

 

 

 

 

 

 

 

 

 

 

 

RS-485 Comm Port #1 Parity

 

 

 

3403

 

0

= Even (default)

0 to 2

 

1

= Odd

 

 

 

 

 

 

￿

2 = None

 

 

 

 

 

RS-485 Comm Port #2 Operation Mode

 

 

 

3430

 

0

= Modbus Slave (default)

0 to 1

 

 

1

= Jbus Slave

 

 

 

 

 

 

 

 

 

 

See “How Power Factor is Stored in the Register” on page 128.

The alternate storage method for power factor (PF) is useful for outputting PF on analog outputs. The PF value is stored as a positive value between 0 and 2, centered around 1 (unity). A value of 0 lagging maps to 0; -0.999 maps to 0.999;0.999 leading maps to 1.001; and 0 leading maps to 2. The alternate PF is also stored with a scale factor 0.001.

These configuration registers require that you enter the setup mode to change the register’s contents. Issue command 9020 to enter setup mode and 9021 to exit setup mode. See “Using the Command Interface to Change Configuration Registers” on page 187 for instructions on

￿how to use the setup-mode commands.

Quantity available for 4-wire system only. Value set to -32,768 if not available.