Appendix A—Abbreviated Register Listing

63230-300-212

Register Listing

April 2001

 

 

Table A–3:Abbreviated Register List

Register

Description

Scale

Units

Register Range

Number

Factor

 

 

 

 

 

 

 

 

2013

Maximum Demand Voltage A-B

D

Volts/Scale

0 to 32,767

 

 

 

 

 

2014 to 2017

Maximum Demand Date/Time Voltage A-B

See Template

See Template

 

 

 

 

 

2018

Minimum Demand Voltage A-B

D

Volts/Scale

0 to 32,767

 

 

 

 

 

2019 to 2022

Minimum Demand Date/Time Voltage A-B

See Template

See Template

 

 

 

 

 

2025

Last Demand Voltage B-C

D

Volts/Scale

0 to 32,767

 

 

 

 

 

2026

Present Demand Voltage B-C

D

Volts/Scale

0 to 32,767

 

 

 

 

 

2027

Running Average Demand Voltage B-C

D

Volts/Scale

0 to 32,767

 

 

 

 

 

2028

Maximum Demand Voltage B-C

D

Volts/Scale

0 to 32,767

 

 

 

 

 

2029 to 2032

Maximum Demand Date/Time Voltage B-C

See Template

See Template

 

 

 

 

 

2033

Minimum Demand Voltage B-C

D

Volts/Scale

0 to 32,767

 

 

 

 

 

2034 to 2037

Minimum Demand Date/Time Voltage B-C

See Template

See Template

 

 

 

 

 

2040

Last Demand Voltage C-A

D

Volts/Scale

0 to 32,767

 

 

 

 

 

2041

Present Demand Voltage C-A

D

Volts/Scale

0 to 32,767

 

 

 

 

 

2042

Running Average Demand Voltage C-A

D

Volts/Scale

0 to 32,767

 

 

 

 

 

2043

Maximum Demand Voltage C-A

D

Volts/Scale

0 to 32,767

 

 

 

 

 

2044 to 2047

Maximum Demand Date/Time Voltage C-A

See Template

See Template

 

 

 

 

 

2048

Minimum Demand Voltage C-A

D

Volts/Scale

0 to 32,767

 

 

 

 

 

2049 to 2052

Minimum Demand Date/Time Voltage C-A

See Template

See Template

 

 

 

 

 

2055

Last Demand Voltage L-L Average

D

Volts/Scale

0 to 32,767

 

 

 

 

 

2056

Present Demand Voltage L-L Average

D

Volts/Scale

0 to 32,767

 

 

 

 

 

2057

Running Average Demand Voltage L-L Average

D

Volts/Scale

0 to 32,767

 

 

 

 

 

2058

Maximum Demand Voltage L-L Average

D

Volts/Scale

0 to 32,767

 

 

 

 

 

2059 to 2062

Maximum Demand Date/Time Voltage L-L Average

See Template

See Template

 

 

 

 

 

2063

Minimum Demand Voltage L-L Average

D

Volts/Scale

0 to 32,767

 

 

 

 

 

2064 to 2067

Minimum Demand Date/Time Voltage L-L Average

See Template

See Template

 

 

 

 

 

2070

Last Demand Voltage A-N

D

Volts/Scale

0 to 32,767

 

 

 

 

 

2071

Present Demand Voltage A-N

D

Volts/Scale

0 to 32,767

 

 

 

 

 

2072

Running Average Demand Voltage A-N

D

Volts/Scale

0 to 32,767

 

 

 

 

 

2073

Maximum Demand Voltage A-N

D

Volts/Scale

0 to 32,767

 

 

 

 

 

2074 to 2077

Maximum Demand Date/Time Voltage A-N

See Template

See Template

 

 

 

 

 

2078

Minimum Demand Voltage A-N

D

Volts/Scale

0 to 32,767

 

 

 

 

 

2079 to 2082

Minimum Demand Date/Time Voltage A-N

See Template

See Template ￿

2085

Last Demand Voltage B-N

D

Volts/Scale

0 to 32,767 ￿

See “How Power Factor is Stored in the Register” on page 128.

The alternate storage method for power factor (PF) is useful for outputting PF on analog outputs. The PF value is stored as a positive value between 0 and 2, centered around 1 (unity). A value of 0 lagging maps to 0; -0.999 maps to 0.999;0.999 leading maps to 1.001; and 0 leading maps to 2. The alternate PF is also stored with a scale factor 0.001.

These configuration registers require that you enter the setup mode to change the register’s contents. Issue command 9020 to enter setup mode and 9021 to exit setup mode. See “Using the Command Interface to Change Configuration Registers” on page 187 for instructions on

￿how to use the setup-mode commands.

Quantity available for 4-wire system only. Value set to -32,768 if not available.