63230-300-212

Chapter 6—Alarms

April 2001

Alarm Conditions and Alarm Numbers

 

 

Table 6–3: List of Default Alarms by Alarm Number

Alarm

Alarm Description

Abbreviated

Test

Units

Scale

Alarm

Number

Display Name

Register

Group

Type

 

 

 

 

 

 

 

 

 

 

 

 

43

Over THD Voltage B–C

Over THD Vbc

1212

Tenths %

 

￿

010

44

Over THD Voltage C–A

Over THD Vca

1213

Tenths %

010

45-80

Reserved for custom alarms.

 

High Speed Alarms (100 ms)

 

 

 

 

 

 

01

Over Current A

Over Ia HS

1,000

Amperes

A

010

02

Over Current B

Over Ib HS

1001

Amperes

A

010

03

Over Current C

Over Ic HS

1002

Amperes

A

010

04

Over Current N

Over In HS

1003

Amperes

B

010

05

Over Current G

Over Ig HS

1004

Amperes

C

010

06

Over Voltage A–N

Over Van HS

1024

Volts

D

010

 

 

 

 

 

 

 

07

Over Voltage B–N

Over Vbn HS

1025

Volts

D

010

 

 

 

 

 

 

 

08

Over Voltage C–N

Over Vcn HS

1026

Volts

D

010

 

 

 

 

 

 

 

09

Over Voltage A-B

Over Vab HS

1020

Volts

D

010

 

 

 

 

 

 

 

10

Over Voltage B-C

Over Vbc HS

1021

Volts

D

010

 

 

 

 

 

 

 

11

Over Voltage C-A

Over Vca HS

1022

Volts

D

010

 

 

 

 

 

 

 

12

Over Voltage N-G

Over Vng HS

1027

Volts

E

010

 

 

 

 

 

 

 

13

Under Voltage A–N

Under Van HS

1024

Volts

D

020

 

 

 

 

 

 

 

14

Under Voltage B–N

Under Vbn HS

1025

Volts

D

020

 

 

 

 

 

 

 

15

Under Voltage C–N

Under Vcn HS

1026

Volts

D

020

 

 

 

 

 

 

 

16

Under Voltage A-B

Under Vab HS

1020

Volts

D

020

 

 

 

 

 

 

 

17

Under Voltage B–C

Under Vbc HS

1021

Volts

D

020

 

 

 

 

 

 

 

18

Under Voltage C–A

Under Vca HS

1022

Volts

D

020

 

 

 

 

 

 

 

 

19-20

Reserved for custom alarms

 

 

 

 

 

 

 

 

 

Disturbance Monitoring (1/2 Cycle)

 

 

 

 

 

 

 

 

 

 

 

 

 

01

Voltage Swell A

Swell Van

4

Volts

D

080

 

 

 

 

 

 

 

02

Voltage Swell B

Swell Vbn

5

Volts

D

080

 

 

 

 

 

 

 

03

Voltage Swell C

Swell Vcn

6

Volts

D

080

 

 

 

 

 

 

 

04

Voltage Swell N–G

Swell Vng

7

Volts

E

080

 

 

 

 

 

 

 

05

Voltage Swell A–B

Swell Vab

1

Volts

D

080

 

 

 

 

 

 

 

06

Voltage Swell B–C

Swell Vbc

2

Volts

D

080

 

 

 

 

 

 

 

07

Voltage Swell C–A

Swell Vca

3

Volts

D

080

 

 

 

 

 

 

 

08

Voltage Sag A–N

Sag Van

4

Volts

D

090

 

 

 

 

 

 

 

09

Voltage Sag B–N

Sag Vbn

5

Volts

D

090

 

 

 

 

 

 

 

10

Voltage Sag C–N

Sag Vcn

6

Volts

D

090

 

 

 

 

 

 

 

11

Voltage Sag A–B

Sag Vab

1

Volts

D

090

 

 

 

 

 

 

 

12

Voltage Sag B–C

Sag Vbc

2

Volts

D

090

 

 

 

 

 

 

 

13

Voltage Sag C–A

Sag Vca

3

Volts

D

090

 

 

 

 

 

 

 

14

Current Swell A

Swell Ia

8

Amperes

A

080

 

 

 

 

 

 

 

15

Current Swell B

Swell Ib

9

Amperes

A

080

 

 

 

 

 

 

 

16

Current Swell C

Swell Ic

10

Amperes

A

080

 

 

 

 

 

 

 

17

Current Swell N

Swell In

11

Amperes

B

080

 

 

 

 

 

 

 

18

Current Sag A

Sag Ia

8

Amperes

A

090

 

 

 

 

 

 

 

19

Current Sag B

Sag Ib

9

Amperes

A

090

 

 

 

 

 

 

 

20

Current Sag C

Sag Ic

10

Amperes

A

090

 

 

 

 

 

 

 

 

Alarm Types are described in Table 6–4 on page 96.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

￿￿

 

 

 

 

 

 

95

© 2001 Schneider Electric All Rights Reserved

 

 

 

 

 

Page 107
Image 107
Schneider Electric 4000 manual Display Name, High Speed Alarms 100 ms, Disturbance Monitoring 1/2 Cycle