63230-300-212 AppendixAAbbreviatedR egisterListing
April 2001 Registe r Listing
151
© 2001 Schneider Electric All Rights Reserved
2086 Present Dem and Voltage B-N D Volts/Scale 0 to 32,767
2087 Running Average Dem and Voltage B-N D Volts/Scale 0 to 32,767
2088 Maximum De mand Voltage B-N D Volts/Scale 0 to 32,767
2089to 2092 MaximumDemand Date/TimeVoltage B-N SeeTemplate SeeTemplate
2093 Minimum Dem and Voltage B-N D Volts/Scale 0 to 32,767
2094 to 2097 Minimum Demand Date/Time Volta ge B-N See Template S ee Template
2100 Last Demand Voltag e C-N D Volts/Scale 0 to 32,767
2101 Present Dem and Voltage C-N D Volts/Scale 0to 32,7 67
2102 Running Average Dem and Voltage C-N D Volts/Sc ale 0 to 32,767
2103 Maximum De mand Voltage C-N D Volts/Scale 0 to 32,767
2104to 2107 MaximumDemand Date/TimeVoltage C-N See Template See Template
2108 Minimum Dem and Voltage C-N D Volts/Scale 0 to 32,767
2109 to 2112 Minimum Demand Date/Time Volta ge C-N See Template See Template
2115 Last Demand Voltag e N-G E Volts/Scale 0 to 32,767
2116 Present Dem and Voltage N-G E Volts/Scale 0to 32,7 67
2117 Running Average Dem and Voltage N-G E Volts/Sc ale 0t o 32,767
2118 Maximum De mand Voltage N-G E Volts/Scale 0 to 32,767
2119to 2122 MaximumDemand Date/TimeVoltage N-G See Template See Template
2123 Minimum Dem and Voltage N-G E Volts/Scale 0 to 32,767
2124 Minimum D emand Date/Time Volta ge N-G See Template See Template
2130 Last Demand Voltag e L-N Average D Volts/Scale 0 to 32,767
2131 Present Dem and Voltage L-N Average D Volts/Scale 0 to 32,767
2132 Running Average Dem and Voltage L-N Average D Volts/Scale 0 to 32,767
2133 Maximum De mand Voltage L-N Average D Volts/Scal e 0to 32,7 67
2134 Maximum De mand Date/Time Voltage L-N Average See Template See Template
2138 Minimum Dem and Voltage L-N Average D Volts/Scale 0 to 32,767
2139 to 2142 Minimum Demand Date/Time Volta ge L-N Average See Template See Template
2150
Last Demand Real Power, 3-Phase Total
3-Phasetotal present real powerdemand for last completed
demand interval, updat ed every sub-interval
F kW/Scale -32,767to 32,767
2151 Present D emand Real Power, 3-Phase Total F kW/Scale - 32,767 to 32,767
2152 RunningAverage DemandReal Power,3-Phase Total F kW/Scale -32,767 to 32,767
Tabl e A3:AbbreviatedRegister List
Register
Number Description Scale
Factor Units Regist er Range
See HowPower Factoris Stored in the Registeronpage 128.
Thealternate storage methodfor power factor(PF) is useful for outputtingPF on analog outputs.The PF value isstored as a positive value
between 0 and 2, centered around 1 (un ity). A value of 0 lagging maps to 0; -0.99 9m aps to 0.999;0.999 leading m aps to 1.001; and 0 leading
mapsto 2. The alternate PF is alsostored with a scale factor0.001.
These configuration r egisters require th at you enter the setup mo de to change the regi sters contents. Issue command 9020 t o enter setup
modeand 9021 to exit setup mode.S ee Usingthe Command Interfaceto Change ConfigurationRegistersonpage 187 for instructions on
howto use the setup-mode commands.
Quantity available for 4-w ire system only. Value set to -32, 768 if not available.