Chapter 3—Operation 63230-300-212
Configuring the Circuit Monitor Using The Setup M enu April 2001
©200 1 Schneider Electric All Rights Reserved
30
In this example,we selected Custom Quantity 1. Table38showsthe
available values.
6. Use the arrow buttons to scroll to the menu option you want to change.
7. Press the enter button to select the value.The value begins to blink. Use
the arrow buttonsto scroll through the available values.Then, press the
enter button to s elect the new value.
8. Use the arrow buttons to scroll throughthe other options on the menu, or
if you arefinished, press the menu button to save.
Anasterisk (*) next to the quantity indicates that the quantity has been added
to the list.
9. To save the changesto the Display Setup screen, pressthe menu button.
The custom quantityis added to the Quantities List in the Custom Screen
Setup.The new quantity appears at the end of this list after the standard
quantities.After creating the custom quantity,you must create a custom
screent o be ableto view the new quantity.
Table3–8: Options for Custom Quantities
Option Available Values Default
Lbl Name of the quant ity up to 10 characters. Press th ea rrow
buttons to scroll through the c haracters. Tom ove to the
next option, press the menu but ton.
Register 4-or 5-dig it number of the reg ister in which the qu antity
exists.
1,000
Scale Multiplier of the registervalue can beone of the following:
.001, .01, .1, 1.0, 10, 100 or 1 ,000. See Scale Factorson
page91 for more information.
1,000
Format Integer
D/Tdateand time
MOD10L4Modulo 10,000 with 4 registers
MOD10L3Modulo 10,000 with 3 registers
MOD10L2Modulo 10,000 with 2 registers
Label
Integer
Modulo 10,000 is used to store energy. See the SMS online help for more.
Usethe L abel format only when a label has been defined with no co rresponding register.
Custom Quantity 1
Lbl:
Register 1,000
Scale 1,000
Format Integer