Appendix A—Abbreviated Register Listing

April 2001

How Power Factor is Stored in the Register

 

 

HOW DATE AND TIME ARE STORED IN THE REGISTER

The date and time are stored in a four-register compressed format. Each of the four registers, such as registers 1810 to 1813, contain a high and low byte value to represent the date and time in hexadecimal. Table A–1lists the register and the portion of the date or time it represents.

Table A–1:Date and Time Format

Register

Hi Byte

 

Lo Byte

 

 

 

 

Register 1

Month (1-12)

 

Day (1-31)

 

 

 

 

Register 2

Year (0-199)

 

Hour (0-23)

 

 

 

 

Register 3

Minute (0-59)

 

Second (0-59)

 

 

 

 

Register 4

 

Milliseconds

 

 

 

 

For example, if the date was 01/25/00 at 11:06:59.122, the Hex value would be 0119, 640B, 063B, 007A. Breaking it down into bytes we have the following:

Table A–2:Date and Time Byte Example

Hexadecimal

 

Hi Byte

 

Lo Byte

Value

 

 

 

 

 

 

 

 

 

 

0119

01

= month

19 = day

 

 

 

 

 

640B

64

= year

0B

= hour

 

 

 

 

 

063B

06

= minute

3B

= seconds

 

 

 

 

007A

 

007A = milliseconds

 

 

 

 

 