Appendix AAbbreviated Regist er Listing 63230-300-212
Register Listing April 2001
©200 1 Schneider Electric All Rights Reserved
152
2153 PredictedDemand Real Power,3-PhaseTotal
Predictedreal powerdemand at the end of the presentinterval F kW/Scale -32,767 to 32 ,767
2154 Peak Demand Rea lPower, 3-Pha se Total F kW /Scale -32,767 to 32,7 67
2155 to 2158 Peak Demand Date/Tim e Real Power, 3-Phase Total SeeTemplate See Template
2159to 2160 CumulativeDemand RealPower, 3-PhaseTotal F kW/Scale -2147483648 to2147483647
2161 Power Factor, Average @ Peak Demand, Real Power 0.001 1,000 -100 to 1 00
2162 PowerDemand, Reactive@ Peak Demand, RealPower F kVAr/Scale -32,767 to 32,767
2163 Power Demand, Appar ent @ Peak Demand, Real Power F kVA/Scale 0 to 32,767
2165 Last Dema nd Reactive Power, 3-Phase Total F kVAr /Scale -32,767 to 32,767
2166 PresentDemand Reactive Power,3-PhaseTotal F kVAr/Scale -32,767 to 32,767
2167 RunningAverage DemandReactive Power,3-Phase Total F kVAr/Scale -32,767to 32,767
2168
PredictedDemand ReactivePower, 3-PhaseTotal
Predictedreactive powerdemand at the end of the present
interval
F kVAr/Sc ale - 32,767 to 32,767
2169 Peak Demand Rea ctive Power,3- Phase Total F kVAr /Scale -32,767 to 32, 767
2170to 2173 PeakDemand Date/Time ReactivePower, 3-PhaseTotal SeeTemplate See Template
2174to 2175 CumulativeDemand ReactivePower,3-Phase Total F kVAr /Scale -2147483648 to 2147483647
2176 Power Factor, Average @ Peak Demand, Rea ctive Power 0. 001 1,000 -100 to 100
2177 PowerDemand, Real @ PeakDemand, ReactivePower F kW/Scale -32,767 to32,767
2178 Power Demand, App arent @ Peak Demand, Reactive Power F kVA/Scale 0 to 32,767
2180 Last Deman dA pparent Power 3-Phase Total F kVA/S cale -32,767 to 32,7 67
2181 PresentDemand Apparent Power,3-Phase Total F kVA/Scale -32,767 to 32,767
2182 RunningAverage DemandApparent Power,3-Phase Total F kVA/Scale -32,767 to 32,767
2183
PredictedDemand ApparentPower, 3-PhaseTotal
Predicted apparent power demand at the end of the present
interval
F kVA/Scale -32,767 to 32,767
2184 PeakDemand Apparent Power,3-PhaseTotal F kVA /Scale -32,767to 32,767
2185to 2188 PeakDemand Date/Time ApparentPower, 3-PhaseTotal See Template See Template
2189to 2190 CumulativeDemand ApparentPower,3-Phase Total F kVA /Scale -2147483648to 2147483647
2191 Power Factor, Average @ Peak Demand, Appare nt Power 0.001 1,000 -100 to 100
2192 PowerDemand, Real @ PeakDemand, Apparent Power F kW/Scale -32,767 to 32,767
2193 PowerDemand, Reactive@ Peak Demand, ApparentPower F kVAr/Scale 0 to 32,767
2200 UnitCode, Input Channel #1
For software use only ——0to99
2201 Scale Code, Input Chann el #1 ——-3to 3, Default= 0
2202 LastDemand, Input Channel#1 ——0 to 32,767, Default = 0
2203 PresentDemand, Input Channel#1 ——0to32,767
Tabl e A3:AbbreviatedRegister List
Register
Number Description Scale
Factor Units Register Range
See How Power Factor is Stored in t he Registeron page 128.
Thealternate storage methodfor power factor(PF) is useful for outputtingPF on analog outputs.The PF valueis stored as a positivevalue
between0 and 2,centered around1 (unity). A valueof 0 lagging mapsto 0; -0.999 mapsto 0.999;0.999 leadingmaps to 1.001;and 0 leading
mapsto 2. The alternate PF is alsostored with a scale factor0.001.
Theseconfiguration registersrequire that youenter the setup mode to change the registerscontents. Issuecommand 9020 to enter setup
mode and 9021 to exit setup mode. See Us ing the Command Interface to Cha nge Configuration Regist erson page 187 for instruction s on
howtousethesetup-modecommands.
Quantity available for 4- wire system only. Value set to - 32,768 if not available.