Chapter 3—Operation

April 2001

 

Configuring the Circuit Monitor Using The Setup Menu

 

 

Creating a New Custom Alarm

In addition to editing an alarm, you can also create new custom alarms by

 

performing two steps:

 

1.

Create the custom alarm.

 

2.

Setup and enable the new alarm.

To use custom alarms, you must first create a custom alarm and then set up the alarm to be used by the circuit monitor. Creating an alarm defines information about the alarm including:

Alarm group (standard, high speed, disturbance, digital, or boolean)

Name of the alarm

Type (such as whether it alarms on an over or under condition)

Register number of the value that will be alarmed upon

To create an alarm, follow these steps:

1.From the Main Menu, select Setup > Alarm > Create Custom. The Create Custom screen displays.

CREATE CUSTOM

 

 

Standard

1 sec

 

 

High Speed

100ms

 

Disturbance

<1cycle

 

Digital

 

 

Boolean

 

2.Select the Alarm Group for the alarm that you are creating:

Standard—detection rate of 1 second

High Speed—detection rate of 100 millisecond

Disturbance—detection rate of less than 1 cycle

Digital—triggered by an exception such as a status input or the end of an interval

Boolean—triggered by condition of alarms used as inputs

The Select Position screen displays and jumps to the first open position in the alarm list.

SELECT POSITION

*43 Over THD Vbc

*44 Over THD Vca

45

3.Select the position of the new alarm. The Alarm Parameters screen displays.

© 2001 Schneider Electric All Rights Reserved

19