63230-300-212 Chapter3Operation
April 2001 Performing a Wiring Chec k
47
© 2001 Schneider Electric All Rights Reserved
2. Select Wiring Error Test from the menu.
The circuitm onitorasks if the wiring matches the test assumptions.
3. Pr essthe down arrow button.
The circuit monitorasks if the expected displacement power factori s
between 0.60 laggingand 0.99 leading.
4. Pr essthe down arrow button, again.
The circuit monito r asks if youdliketoperformawiringcheck.
5. Select Ye s to perform the test by pressing theup arrow button and then
pressing the enter button.
The circuit monitorperforms the wiring test.
If it doesnt findany errors, the circuit monitor displaysWire test
complete.N o errors found!.If it finds possible errors, it displaysError
detected. See followingscreens for details.
6. Press the arrow buttons to scroll through the wiring error messages.
Tabl e 312 on page 48explains the possible wiring errormessages.
7. Turn off all power supplying the circuitmonitor. Verifythat the power is off
using a properly ratedvoltage testing device.
Test Assumptions:
Va and Vn for 4wire
Va and Vb for 3wire
are correct.
Test Assumptions:
Displacement PF is
between 0.60 lag
and 0.99 lead.
Perform Test No