63230-300-212 Chapter9Disturban ceM onitoring
April 2001 About Disturbance M onitoring
115
© 2001 Schneider Electric All Rights Reserved
A voltage sag isa brief (1/4 cycle to 1 minute) decrease in rms voltage
magnitude.A sag is typicallycaused by a remote fault somewhere on the
power system,often initiated by a lightning strike. In Figure 91, the utility
circuitbr eakercleared the fault near plant D.The fault not only caused an
interruptionto plant D, but also resultedin voltage sags to plants A, B,and C.
NOTE: TheCM 4000i s ableto detect sag and swell eventsless than 1/4 cycleduration. However,it may be impractical to havesetpoints more sensitivethan 10% for voltageand current fluctuations.
Figure 91: A fault can cause voltage sag on the whole system.
System voltagesags are much more numerous than interruptions, since a
wider part of the distributionsystem is affected. And, if reclosers are
operating,they may cause repeated sags. The circuit monitor can record
recloser sequences,too. The waveform in Figure92 shows the magnitude
of a voltagesag, which persists until the remotefault is cleared.
Figure 92: Waveform showing voltage sag, whichwas causedby a
remote fault and las ted five cycles.
X
Utility
Circuit Breakers
with Reclosers
Utility
Transformer
1 Plant A
2 Plant B
3 Plant C
4 Plant D
Fault
A faultnear plant D, clearedby the utility
circuit breaker, can stil l affect plants A, B,
andC, resulting in a voltagesag.