63230-300-212 AppendixAAbbreviatedR egisterListing
April 2001 Registe r Listing
131
© 2001 Schneider Electric All Rights Reserved
1065 Alterna te TruePower Factor, Phase B 0.001 0 to 2 ,000
1066 Alterna te TruePower Factor, Phase C 0.001 0 to 2,00 0
1067 Alterna te TruePower Factor, Total 0.001 0 to 2,000
1-SecondReal-Time Readings
1100 Current, Ph ase A A Amps/Scale 0to 3 2,767
1101 Current, Ph ase B A Amps/Scale 0to 3 2,767
1102 Current, Ph ase C A Amps/Scale 0 to 3 2,767
1103 Current, Ne utral B Amps/Scale 0to 3 2,767
1104 Current, Gro und C Amps/Scale 0 to 32,767
1105 Current, 3-P hase Average A Amp s/Scale 0 to 32,7 67
1106 Current, App arent RMS A Amps/Sc ale 0 to 32,767
1107 Current, U nbalance, Phase A 0.10% -1,000 to 1,000
1108 Current, U nbalance, Phase B 0.10% -1,000 to 1,000
1109 Current, U nbalance, Phase C 0.10% -1,000to 1,000
1110 Current,Unbalance, Max 0.10% -1,000 to 1,000
1120 Voltage, A-B D Volts/Scale 0to 3 2,767
1121 Voltage, B-C D Volts/Scale 0to 32,7 67
1122 Voltage, C-A D Volts/Scale 0to 32,7 67
1123 Voltage, L-L Average D Volts/Scal e 0to 3 2,767
1124 Voltage, A-N D Volts/Scale 0to 32,7 67
1125 Voltage, B-N D Volts/Scale 0to 32,7 67
1126 Voltage, C-N D Volts /Scale 0 to 32,767
1127 Voltage, N-G E Volts/Scale 0 to 32,767
1128 Voltage, L-N Average D Volts/Scale 0 to 32,767
1129 Voltage, Unbala nce, A-B 0.10% -1,000 to 1,000
1130 Voltage, Unbala nce, B-C 0.10% -1,000 to 1,000
1131 Voltage, Unbala nce, C-A 0.10% -1,000 to 1,000
1132 Voltage, Unbala nce, Max L-L 0.10% -1,000 to 1,000
1133 Voltage, Unbala nce, A-N 0.10% -1,000 to 1,000
1134 Voltage, Unbala nce, B-N 0.10% -1,000 to 1,000
1135 Voltage, Unbala nce, C-N 0.10% -1,000 to 1,000
1136 Voltage, Unbala nce, Max L-N 0.10% -1,000to 1,000
1140 RealPower, Phase A F kW/Scale -32,767 to 32,767
1141 RealPower, Phase B F kW/Scale -32,767 to 32,767
1142 RealPower, Phase C F kW/Scale -32,767to 32,767
1143 Real Power, Total F kW/Scale -32,767 to 32,767
Tabl e A3:AbbreviatedRegister List
Register
Number Description Scale
Factor Units Regist er Range
See HowPower Factoris Stored in the Registeronpage 128.
Thealternate storage methodfor power factor(PF) is useful for outputtingPF on analog outputs.The PF value isstored as a positive value
between 0 and 2, centered around 1 (un ity). A value of 0 lagging maps to 0; -0.99 9m aps to 0.999;0.999 leading m aps to 1.001; and 0 leading
mapsto 2. The alternate PF is alsostored with a scale factor0.001.
These configuration r egisters require th at you enter the setup mo de to change the regi sters contents. Issue command 9020 t o enter setup
modeand 9021 to exit setup mode.S ee Usingthe Command Interfaceto Change ConfigurationRegistersonpage 187 for instructions on
howto use the setup-mode commands.
Quantity available for 4-w ire system only. Value set to -32, 768 if not available.