63230-300-212

Appendix A—Abbreviated Register Listing

April 2001

Register Listing

 

 

Table A–3:Abbreviated Register List

Register

Description

Scale

Units

Register Range

 

Number

Factor

 

 

 

 

 

 

 

 

 

 

 

1065

Alternate True Power Factor, Phase B

0.001

0 to 2,000

 

 

 

 

 

 

 

1066

Alternate True Power Factor, Phase C

0.001

0 to 2,000 ￿

 

 

 

 

 

 

 

1067

Alternate True Power Factor, Total

0.001

0 to 2,000 ￿

 

 

 

 

 

 

 

1-Second Real-Time Readings

 

 

 

 

 

 

 

 

 

 

1100

Current, Phase A

A

Amps/Scale

0 to 32,767

 

 

 

 

 

 

 

1101

Current, Phase B

A

Amps/Scale

0 to 32,767

 

 

 

 

 

 

 

1102

Current, Phase C

A

Amps/Scale

0 to 32,767

 

 

 

 

 

 

 

1103

Current, Neutral

B

Amps/Scale

0 to 32,767

 

 

 

 

 

 

 

1104

Current, Ground

C

Amps/Scale

0 to 32,767 ￿

 

 

 

 

 

 

 

1105

Current, 3-Phase Average

A

Amps/Scale

0 to 32,767

 

 

 

 

 

 

 

1106

Current, Apparent RMS

A

Amps/Scale

0 to 32,767

 

 

 

 

 

 

 

1107

Current, Unbalance, Phase A

0.10%

-1,000 to 1,000

 

 

 

 

 

 

 

1108

Current, Unbalance, Phase B

0.10%

-1,000 to 1,000

 

 

 

 

 

 

 

1109

Current, Unbalance, Phase C

0.10%

-1,000 to 1,000

 

 

 

 

 

 

 

1110

Current, Unbalance, Max

0.10%

-1,000 to 1,000

 

 

 

 

 

 

 

1120

Voltage, A-B

D

Volts/Scale

0 to 32,767

 

 

 

 

 

 

 

1121

Voltage, B-C

D

Volts/Scale

0 to 32,767

 

 

 

 

 

 

 

1122

Voltage, C-A

D

Volts/Scale

0 to 32,767

 

 

 

 

 

 

 

1123

Voltage, L-L Average

D

Volts/Scale

0 to 32,767

 

 

 

 

 

 

 

1124

Voltage, A-N

D

Volts/Scale

0 to 32,767

 

 

 

 

 

 

 

1125

Voltage, B-N

D

Volts/Scale

0 to 32,767

 

 

 

 

 

 

 

1126

Voltage, C-N

D

Volts/Scale

0 to 32,767

 

 

 

 

 

 

 

1127

Voltage, N-G

E

Volts/Scale

0 to 32,767 ￿

 

 

 

 

 

 

 

1128

Voltage, L-N Average

D

Volts/Scale

0 to 32,767

 

 

 

 

 

 

 

1129

Voltage, Unbalance, A-B

0.10%

-1,000 to 1,000

 

 

 

 

 

 

 

1130

Voltage, Unbalance, B-C

0.10%

-1,000 to 1,000

 

 

 

 

 

 

 

1131

Voltage, Unbalance, C-A

0.10%

-1,000 to 1,000

 

 

 

 

 

 

 

1132

Voltage, Unbalance, Max L-L

0.10%

-1,000 to 1,000

 

 

 

 

 

 

 

1133

Voltage, Unbalance, A-N

0.10%

-1,000 to 1,000

 

 

 

 

 

 

 

1134

Voltage, Unbalance, B-N

0.10%

-1,000 to 1,000

 

 

 

 

 

 

 

1135

Voltage, Unbalance, C-N

0.10%

-1,000 to 1,000

 

 

 

 

 

 

 

1136

Voltage, Unbalance, Max L-N

0.10%

-1,000 to 1,000 ￿

 

1140

Real Power, Phase A

F

kW/Scale

-32,767 to 32,767

 

 

 

 

 

 

 

1141

Real Power, Phase B

F

kW/Scale

-32,767 to 32,767

 

 

 

 

 

 

 

1142

Real Power, Phase C

F

kW/Scale

-32,767 to 32,767

 

 

 

 

 

 

 

1143

Real Power, Total

F

kW/Scale

-32,767 to 32,767

￿

See “How Power Factor is Stored in the Register” on page 128.

The alternate storage method for power factor (PF) is useful for outputting PF on analog outputs. The PF value is stored as a positive value between 0 and 2, centered around 1 (unity). A value of 0 lagging maps to 0; -0.999 maps to 0.999;0.999 leading maps to 1.001; and 0 leading maps to 2. The alternate PF is also stored with a scale factor 0.001.

These configuration registers require that you enter the setup mode to change the register’s contents. Issue command 9020 to enter setup mode and 9021 to exit setup mode. See “Using the Command Interface to Change Configuration Registers” on page 187 for instructions on

￿how to use the setup-mode commands.

Quantity available for 4-wire system only. Value set to -32,768 if not available.