Appendix A—Abbreviated Register Listing

April 2001

Register Listing

 

 

Table A–3:Abbreviated Register List

Register

Description

Scale

Units

Register Range

Number

Factor

 

 

 

 

 

 

 

 

1277

Harmonic Current, Neutral

B

Amps/Scale

0 to 32,767

 

 

 

 

 

1278

Harmonic Voltage, A-N/A-B

D

Volts/Scale

0 to 32,767 ￿

 

 

 

 

 

1279

Harmonic Voltage, B-N/B-C

D

Volts/Scale

0 to 32,767

 

 

 

 

 

1280

Harmonic Voltage, C-N/C-A

D

Volts/Scale

0 to 32,767

 

 

 

 

 

1281

Total Demand Distortion

0.1%

0 to 1,000

 

 

 

 

 

1284

Current, Positive Sequence, Magnitude

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1285

Current, Positive Sequence, Angle

0.1°

0 to 3,599

 

 

 

 

 

1286

Current, Negative Sequence, Magnitude

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1287

Current, Negative Sequence, Angle

0.1°

0 to 3,599

 

 

 

 

 

1288

Current, Zero Sequence, Magnitude

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1289

Current, Zero Sequence, Angle

0.1°

0 to 3,599

 

 

 

 

 

1290

Voltage, Positive Sequence, Magnitude

D

Volts/Scale

0 to 32,767

 

 

 

 

 

1291

Voltage, Positive Sequence, Angle

0.1°

0 to 3,599

 

 

 

 

 

1292

Voltage, Negative Sequence, Magnitude

D

Volts/Scale

0 to 32,767

 

 

 

 

 

1293

Voltage, Negative Sequence, Angle

0.1°

0 to 3,599

 

 

 

 

 

1294

Voltage, Zero Sequence, Magnitude

D

Volts/Scale

0 to 32,767

 

 

 

 

 

1295

Voltage, Zero Sequence, Angle

0.1°

0 to 3,599

 

 

 

 

 

1296

Current, Sequence, Unbalance

0.10%

0 to 32,767

 

 

 

 

 

1297

Voltage, Sequence, Unbalance

0.10%

0 to 32,767

 

 

 

 

 

Real to Time Minimum Metered Values

 

 

 

 

 

 

 

 

1300

Minimum Current, Phase A

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1301

Minimum Current, Phase B

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1302

Minimum Current, Phase C

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1303

Minimum Current, Neutral

B

Amps/Scale

0 to 32,767

 

 

 

 

 

1304

Minimum Current, Ground

C

Amps/Scale

0 to 32,767 ￿

 

 

 

 

 

1305

Minimum Current, 3-Phase Average

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1306

Minimum Current, Apparent RMS

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1307

Minimum Current Unbalance, Phase A

0.10%

-1,000 to 1,000

 

 

 

 

 

1308

Minimum Current Unbalance, Phase B

0.10%

-1,000 to 1,000

 

 

 

 

 

1309

Minimum Current Unbalance, Phase C

0.10%

-1,000 to 1,000

 

 

 

 

 

1310

Minimum Current Unbalance, Max

0.10%

-1,000 to 1,000

 

 

 

 

 

1320

Minimum Voltage, A-B

D

Volts/Scale

0 to 32,767

 

 

 

 

 

1321

Minimum Voltage, B-C

D

Volts/Scale

0 to 32,767

 

 

 

 

 

1322

Minimum Voltage, C-A

D

Volts/Scale

0 to 32,767

 

 

 

 

 

1323

Minimum Voltage, L-L Average

D

Volts/Scale

0 to 32,767

 

 

 

 

 

1324

Minimum Voltage, A-N

D

Volts/Scale

0 to 32,767

 

 

 

 

 

See “How Power Factor is Stored in the Register” on page 128.

The alternate storage method for power factor (PF) is useful for outputting PF on analog outputs. The PF value is stored as a positive value between 0 and 2, centered around 1 (unity). A value of 0 lagging maps to 0; -0.999 maps to 0.999;0.999 leading maps to 1.001; and 0 leading maps to 2. The alternate PF is also stored with a scale factor 0.001.

These configuration registers require that you enter the setup mode to change the register’s contents. Issue command 9020 to enter setup mode and 9021 to exit setup mode. See “Using the Command Interface to Change Configuration Registers” on page 187 for instructions on

￿how to use the setup-mode commands.

Quantity available for 4-wire system only. Value set to -32,768 if not available.￿