63230-300-212

Chapter 3—Operation

April 2001

Performing a Wiring Check

 

 

Table 3–12: Wiring Error Messages

Message

Description

 

 

Suspected error: Polarity on V3–1 VT

Polarity of V3–1 VT could be reversed. Check polarity.

 

 

Suspected error: Check V1 input, may be V2 VT

Phase 2 VT may actually be connected to input V1.

 

 

Suspected error: Check V2 input, may be V3 VT

Phase 3 VT may actually be connected to input V12

 

 

Suspected error: Check V3 input, may be V1 VT

Phase 1 VT may actually be connected to input V3.

 

 

Suspected error: Check V1 input, may be V3 VT

Phase 3 VT may actually be connected to input V1.

 

 

Suspected error: Check V2 input, may be V1 VT

Phase 1 VT may actually be connected to input V2.

 

 

Suspected error: Check V3 input, may be V2 VT

Phase 2 VT may actually be connected to input V3.

 

 

I1 load current less than 1% CT

Metered current on I1 less than 1% of CT. Test could not continue.

 

 

I2 load current less than 1% CT

Metered current on I2 less than 1% of CT. Test could not continue.

 

 

I3 load current less than 1% CT

Metered current on I3 less than 1% of CT. Test could not continue.

 

 

I1 phase angle out of range. Cause of error unknown.

I1 phase angle is out of expected range. Cause of error unable to

be determined.

 

 

 

I2 phase angle out of range. Cause of error unknown

I2 phase angle is out of expected range. Cause of error unable to

be determined.

 

 

 

I3 phase angle out of range. Cause of error unknown.

I3 phase angle is out of expected range. Cause of error unable to

be determined.

 

 

 

Suspected error: Reverse polarity on I1 CT.

Polarity of I1 CT could be reversed. Check polarity.

 

 

Suspected error: Reverse polarity on I2 CT

Polarity of I2 CT could be reversed. Check polarity.

 

 

Suspected error: Reverse polarity on I3 CT

Polarity of I3 CT could be reversed. Check polarity.

 

 

Suspected error: Check I1 input, may be I2 CT

Phase 2 CT may actually be connected to input I1.

 

 

Suspected error: Check I2 input, may be I3 CT

Phase 3 CT may actually be connected to input I2.

 

 

Suspected error: Check I3 input, may be I1 CT

Phase 1 CT may actually be connected to input I3.

 

 

Suspected error: Check I1 input, may be I3 CT

Phase 3 CT may actually be connected to input I1.

 

 

Suspected error: Check I2 input, may be I1 CT

Phase 1 CT may actually be connected to input I2.

 

 

Suspected error: Check I3 input, may be I2 CT

Phase 2 CT may actually be connected to input I3.

 

 

Suspected error: Check I1 input, may be I2 CT with reverse polarity

Phase 2 CT may actually be connected to input I1, and the CT

polarity may also be reversed.

 

 

 

Suspected error: Check I2 input, may be I3 CT with reverse polarity

Phase 3 CT may actually be connected to input I21, and the CT

polarity may also be reversed.

 

 

 

Suspected error: Check I3 input, may be I1 CT with reverse polarity

Phase 1 CT may actually be connected to input I3, and the CT

polarity may also be reversed.

 

 

 

Suspected error: Check I1 input, may be I3 CT with reverse polarity

Phase 3 CT may actually be connected to input I1, and the CT

polarity may also be reversed.

 

 

 

Suspected error: Check I2 input, may be I1 CT with reverse polarity

Phase 1 CT may actually be connected to input I2, and the CT

polarity may also be reversed.

 

 

 

Suspected error. Check I3 input, may be I2 CT with reverse polarity

Phase 2 CT may actually be connected to input I3, and the CT

polarity may also be reversed.

 

 

 

© 2001 Schneider Electric All Rights Reserved

49

Page 61
Image 61
Schneider Electric 4000 manual I2 load current less than 1% CT