63230-300-212 Chapter3—Operation
April 2001 Configuring the Circuit Monitor Using Th eS etup Menu
21
© 2001 Schneider Electric All Rights Reserved
Toset up a newly createdcustom alarm for use by the circuitmonitor, use the
Edit Parametersoption on the Alarm screen. You can alsochange
parametersof any alarm, new or existing. For example,using the Edit option
youcan enable or disable an alarm, changeits priority, and changeits pickup
and dropout setpoints.
Followthese instructions to set up or edit an alarm:
1. From the Main Menu, select Setup > Alarm > Edit Parameters.
The Edit Parametersscreen displays.
2. Select the Alarm Group:
Standard
High Speed
Disturbance
Digital
Boolean
The Select Alarm screen displays.
NOTE: Ifyou are setting up or editing a digital alarm, alarm names suchas Breaker 1 trip,Breaker 1 reset will display instead.
3. Select the alarm you want to set up or edit.
The Edit Alarm screen with the alarm parametersdisplays. Table35
describes the optionson this menu.
Setting Up andEditing Alarms
EDIT PARAMETERS
Standard 1 sec
High Speed 100ms
Disturbance <1cycle
Digital
Boolean
SELECT ALARM
*01 Over Ia
02 Over Ib
03 Over Ic
EDIT ALARM
Lbl:Over Ia
Enable No
Priority None
Setpoint Mode Abs
Pickup 0
PU Dly seconds 0
Dropout 0
DO Dly seconds 0