Chapter 3—Operation

April 2001

Resetting Min/Max, Demand, and Energy Values

 

 

RESETTING MIN/MAX, DEMAND, AND ENERGY VALUES

A reset clears the circuit monitor’s memory of the last recorded value. For example, you might need to reset monthly peak demand power. From the Reset menu, shown in Figure 3–6,you can reset the following values:

Energy—accumulated energy and conditional energy

Demand—peak power demand and peak current demand

Min/Max—minimum and maximum values for all real-time readings

MAIN MENU

 

RESETS

 

Meters

 

 

Energy

 

 

 

 

Min/Max

 

 

Demand

 

View Alarms

 

 

Min/Max

 

I/O Display

 

 

 

 

Resets

 

 

 

 

 

 

 

 

Setup

 

 

 

 

Diagnostics

 

 

 

 

 

Figure 3–6: Performing resets from the Reset menu

 

 

A password is required to reset any of the options on the Reset menu. The

 

 

default password is 0. See “Setting Up Passwords” on page 27 for more

 

 

information about passwords.

 

 

You can perform resets from the circuit monitor as described in this section

 

 

or if you are using SMS, you can set up a task to perform the reset

 

 

automatically at a specified time. See the SMS online help for instructions.

 

 

NOTE: To stop users from using the display to reset energy, peak demand,

 

 

and min/max values, see “Advanced Meter Setup” on page 34 for instructions

 

 

on using the reset locking feature.

To perform resets, follow these steps:

1.From the Main Menu, select Resets. The Resets menu displays.

RESETS

Energy

Demand

Min/Max

2.Use the arrow buttons to scroll through the menu options on the Resets menu. To select a menu option, press the enter button.

Depending on the option you selected, the screen for that value displays.

RESET ENERGY

 

RESET DEMAND

 

 

RESET MIN/MAX

 

 

Accumulated

No

 

PK

Power Demand

No

 

 

Min/Max

No

 

 

 

 

 

 

 

PK

Amp Demand

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 