Appendix A—Abbreviated Register Listing

April 2001

Register Listing

 

 

Table A–3:Abbreviated Register List

Register

Description

Scale

Units

Register Range

Number

Factor

 

 

 

 

 

 

 

 

1466

Minimum Distortion Power, Phase C

F

kW/Scale

-32,767 to 32,767

 

 

 

 

 

1467

Minimum Distortion Power, Total

F

kW/Scale

-32,767 to 32,767 ￿

 

 

 

 

 

1468

Minimum Distortion Power Factor, Phase A

0.10%

0 to 1,000

 

 

 

 

 

1469

Minimum Distortion Power Factor, Phase B

0.10%

0 to 1,000

 

 

 

 

 

1470

Minimum Distortion Power Factor, Phase C

0.10%

0 to 1,000 ￿

 

 

 

 

 

1471

Minimum Distortion Power Factor, Total

0.10

0 to 1,000

 

 

 

 

 

1474

Minimum Harmonic Current, Phase A

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1475

Minimum Harmonic Current, Phase B

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1476

Minimum Harmonic Current, Phase C

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1477

Minimum Harmonic Current, Neutral

B

Amps/Scale

0 to 32,767

 

 

 

 

 

1478

Minimum Harmonic Voltage, A-N/A-B

D

Volts/Scale

0 to 32,767 ￿

 

 

 

 

 

1479

Minimum Harmonic Voltage, B-N/B-C

D

Volts/Scale

0 to 32,767

 

 

 

 

 

1480

Minimum Harmonic Voltage, C-N/C-A

D

Volts/Scale

0 to 32,767

 

 

 

 

 

1481

Minimum Total Demand Distortion

0.01

0 to 10,000

 

 

 

 

 

1484

Minimum Current, Positive Sequence, Magnitude

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1485

Minimum Current, Positive Sequence, Angle

0.1

0 to 3,599

 

 

 

 

 

1486

Minimum Current, Negative Sequence, Magnitude

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1487

Minimum Current, Negative Sequence, Angle

0.1

0 to 3,599

 

 

 

 

 

1488

Minimum Current, Zero Sequence, Magnitude

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1489

Minimum Current, Zero Sequence, Angle

0.1

0 to 3,599

 

 

 

 

 

1490

Minimum Voltage, Positive Sequence, Magnitude

D

Volts/Scale

0 to 32,767

 

 

 

 

 

1491

Minimum Voltage, Positive Sequence, Angle

0.1

0 to 3,599

 

 

 

 

 

1492

Minimum Voltage, Negative Sequence, Magnitude

D

Volts/Scale

0 to 32,767

 

 

 

 

 

1493

Minimum Voltage, Negative Sequence, Angle

0.1

0 to 3,599

 

 

 

 

 

1494

Minimum Voltage, Zero Sequence, Magnitude

D

Volts/Scale

0 to 32,767

 

 

 

 

 

1495

Minimum Voltage, Zero Sequence, Angle

0.1

0 to 3,599

 

 

 

 

 

1496

Minimum Current, Sequence, Unbalance

0.10%

-1,000 to 1,000

 

 

 

 

 

1497

Minimum Voltage, Sequence, Unbalance

0.10%

-1,000 to 1,000

 

 

 

 

 

Real to Time Maximum Metered Values

 

 

 

 

 

 

 

 

1500

Maximum Current, Phase A

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1501

Maximum Current, Phase B

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1502

Maximum Current, Phase C

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1503

Maximum Current, Neutral

B

Amps/Scale

0 to 32,767

 

 

 

 

 

See “How Power Factor is Stored in the Register” on page 128.

The alternate storage method for power factor (PF) is useful for outputting PF on analog outputs. The PF value is stored as a positive value between 0 and 2, centered around 1 (unity). A value of 0 lagging maps to 0; -0.999 maps to 0.999;0.999 leading maps to 1.001; and 0 leading maps to 2. The alternate PF is also stored with a scale factor 0.001.

These configuration registers require that you enter the setup mode to change the register’s contents. Issue command 9020 to enter setup mode and 9021 to exit setup mode. See “Using the Command Interface to Change Configuration Registers” on page 187 for instructions on

￿how to use the setup-mode commands.

Quantity available for 4-wire system only. Value set to -32,768 if not available.￿