Appendix AAbbreviated Regist er Listing 63230-300-212
Register Listing April 2001
©200 1 Schneider Electric All Rights Reserved
160
3227
Operating Mode Parameters
ModeControl Bits (Default = 0)
Bit 00 = Reserved
Bit01 = Reactive Energy& Demand Accumulation
0 = Fund.Only ; 1 = Harmonics Included
Bit 02 = VAR/PFSign Co nvention
0 = StandardIEEE Convention
1 = CM1 Convention
Bit 03 = Reserved
Bit 04 = Reserved
Bit 05 = Reserved
Bit 06 = Conditional Energy Acc umulation Control
0 = Inputs;1 = Command
Bit 07 = Reserved
Bit 08 = Display Setup
0=Enabled;1=Disabled
Bit 09 = Normal P hase Rotation
0 = ABC; 1 = CBA
Bit10=LargeorSmallTHD
0 = THD; 1= thd
Bit 11 = Generate Phase Loss Voltage
0 = Disabled; 1 = Enabled
Bitmap 0x0000 to 0x0FFF
3228 Metered Phase Rotation Direction
0 = ABC; 1 = CBA ——0to1
3229 IncrementalEnergy Interval
0 = ContinuousAccumulation Minutes 0t o 1440, Default = 60
3230 IncrementalEnergy IntervalStart Time
Value is time represented in minut esf rom midnight Minutes 0 to 1 440, Default = 0
3231 IncrementalEnergy IntervalEnd Time
Value is time represented in minut esf rom midnight Minutes 0 to 1 440, Default = 1440
3232
Energy Accumulation Mo de
Real and Reactive Energy Acc umulation Mode
0 = Absolute(default);1 = Signed
——0to1
3233
Peak Current Demand Over Last Year
Entered by the user for use in calcul ation of Total Demand
Distortion.
0 =Calculation not performed(default)
Amps 0to32,767
3234 NominalSystem Line-to-LineVoltage
Used for diagnostics and alar m D Volts/Scale 0 t o 32,767
3235 NominalCi rcuit Current
Used for diagnostics and alar ms A Amps/Scale 0to 32,767
3240
Harmonic Quantity Selectio n
0 = Disabled
1 = Harmonic magnitud es only (default)
2 = Harmonic magnitud es and angles
——0to2
Tabl e A3:AbbreviatedRegister List
Register
Number Description Scale
Factor Units Register Range
See How Power Factor is Stored in t he Registeron page 128.
Thealternate storage methodfor power factor(PF) is useful for outputtingPF on analog outputs.The PF valueis stored as a positivevalue
between0 and 2,centered around1 (unity). A valueof 0 lagging mapsto 0; -0.999 mapsto 0.999;0.999 leadingmaps to 1.001;and 0 leading
mapsto 2. The alternate PF is alsostored with a scale factor0.001.
Theseconfiguration registersrequire that youenter the setup mode to change the registerscontents. Issuecommand 9020 to enter setup
mode and 9021 to exit setup mode. See Us ing the Command Interface to Cha nge Configuration Regist erson page 187 for instruction s on
howtousethesetup-modecommands.
Quantity available for 4- wire system only. Value set to - 32,768 if not available.