Appendix A—Abbreviated Register Listing

63230-300-212

Register Listing

April 2001

 

 

Table A–3:Abbreviated Register List

Register

Description

Scale

Units

Register Range

Number

Factor

 

 

 

 

 

 

 

 

 

 

 

Operating Mode Parameters

 

 

 

 

 

Mode Control Bits (Default = 0)

 

 

 

 

 

Bit 00 = Reserved

 

 

 

 

 

Bit 01 = Reactive Energy & Demand Accumulation

 

 

 

 

 

0 = Fund. Only ; 1 = Harmonics Included

 

 

 

 

 

Bit 02 = VAR/PF Sign Convention

 

 

 

 

 

0 = Standard IEEE Convention

 

 

 

 

 

1 = CM1 Convention

 

 

 

 

 

Bit 03 = Reserved

 

 

 

 

 

Bit 04 = Reserved

 

 

 

3227

 

Bit 05 = Reserved

Bitmap

0x0000 to 0x0FFF

 

Bit 06 = Conditional Energy Accumulation Control

 

 

 

 

 

 

 

0 = Inputs; 1 = Command

 

 

 

 

 

Bit 07 = Reserved

 

 

 

 

 

Bit 08 = Display Setup

 

 

 

 

 

0 = Enabled; 1 = Disabled

 

 

 

 

 

Bit 09 = Normal Phase Rotation

 

 

 

 

 

0 = ABC; 1 = CBA

 

 

 

 

 

Bit 10 = Large or Small THD

 

 

 

 

 

0 = THD; 1 = thd

 

 

 

 

 

Bit 11 = Generate Phase Loss Voltage

 

 

 

 

 

0 = Disabled; 1 = Enabled

 

 

 

 

 

 

 

 

 

3228

 

Metered Phase Rotation Direction

0 to 1

 

0 = ABC; 1 = CBA

 

 

 

 

 

 

 

 

 

 

 

3229

 

Incremental Energy Interval

Minutes

0 to 1440, Default = 60

 

0 = Continuous Accumulation

 

 

 

 

 

 

 

 

 

 

 

3230

 

Incremental Energy Interval Start Time

Minutes

0 to 1440, Default = 0

 

Value is time represented in minutes from midnight

 

 

 

 

 

 

 

 

 

 

 

3231

 

Incremental Energy Interval End Time

Minutes

0 to 1440, Default = 1440

 

Value is time represented in minutes from midnight

 

 

 

 

 

 

 

 

 

 

 

 

￿

Energy Accumulation Mode

 

 

 

3232

Real and Reactive Energy Accumulation Mode

0 to 1

 

0 = Absolute (default); 1 = Signed

 

 

 

 

 

Peak Current Demand Over Last Year

 

 

 

3233

 

Entered by the user for use in calculation of Total Demand

Amps

0 to 32,767

 

Distortion.

 

 

 

 

 

 

 

0 = Calculation not performed (default)

 

 

 

 

 

 

 

 

 

3234

 

Nominal System Line-to-Line Voltage

D

Volts/Scale

0 to 32,767

 

Used for diagnostics and alarm

 

 

 

 

 

 

 

 

 

 

 

3235

 

Nominal Circuit Current

A

Amps/Scale

0 to 32,767

 

Used for diagnostics and alarms

 

 

 

 

 

 

 

 

 

 

 

 

 

Harmonic Quantity Selection

 

 

 

3240

 

0 = Disabled

0 to 2

 

1 = Harmonic magnitudes only (default)

 

 

 

 

 

 

￿

2 = Harmonic magnitudes and angles

 

 

 

See “How Power Factor is Stored in the Register” on page 128.

The alternate storage method for power factor (PF) is useful for outputting PF on analog outputs. The PF value is stored as a positive value between 0 and 2, centered around 1 (unity). A value of 0 lagging maps to 0; -0.999 maps to 0.999;0.999 leading maps to 1.001; and 0 leading maps to 2. The alternate PF is also stored with a scale factor 0.001.

These configuration registers require that you enter the setup mode to change the register’s contents. Issue command 9020 to enter setup mode and 9021 to exit setup mode. See “Using the Command Interface to Change Configuration Registers” on page 187 for instructions on

￿how to use the setup-mode commands.

Quantity available for 4-wire system only. Value set to -32,768 if not available.