63230-300-212

Appendix A—Abbreviated Register Listing

April 2001

Register Listing

 

 

Table A–4:Abbreviated Register List for I/O Status

Register

Name

Units

Range

Description

Number

 

 

 

 

 

 

 

 

 

 

 

 

 

Bitmap of Time Sync Signal Health Status:

 

 

 

 

0 = OK, 1 = Error

 

 

 

 

Bit 00 = Summary Bit , time sync signal fatal error

 

Time Sync Signal

 

0x0000 to

Bit 01 = Lost time sync signal

4016

Bit 02 = Summary Bit , invalid data

Health Status

0xFFFF

 

 

Bit 12 = Good time sync signal received

 

 

 

 

 

 

 

 

Bit 13 = Reserve antenna in use

 

 

 

 

Bit 14 = DST warning

 

 

 

 

Bit 15 = DST in effect

 

 

 

 

 

4017

GPS Time Sync

milli-

0 to 1,000

GPS Time Sync Accuracy

Accuracy

seconds

 

 

 

 

 

 

 

 

 

 

 

 

Indicates the type of Option Module present in Option Slot A.

4021

Present Module Type

0 to 7

0 = Not Installed

Option Slot A

1 = IOC44

 

 

 

 

 

 

 

6 = Ethernet Option Module

 

 

 

 

 

 

 

 

 

Indicates the type of Option Module present in Option Slot B.

4022

Present Module Type

0 to 7

0 = Not Installed

Option Slot B

1 = IOC44

 

 

 

 

 

 

 

6 = Ethernet Option Module

 

 

 

 

 

 

Present Module Type

 

 

Indicates the presence of the pluggable IO rack.

4023

0, 5

0 = No module present

Pluggable IO

 

 

 

5 = Pluggable IO rack present

 

 

 

 

 

 

 

 

 

4200–4299

Digital Output/Alarm

0 to 17081

Table of digital output/alarm associations. Upper byte is IO Point

Table

Number (1 to 66). Lower byte is Alarm Index Number (1 to 185).

 

 

 

 

 

 

 

 

 

IO Point Number 1

 

 

 

4300–4329

Standard Digital

 

 

Refer to digital Output template below.

 

Output (KYZ)

 

 

 

 

 

 

 

 

4360–4389

IO Point Number 3

 

 

Register contents depend on IO Point Type. Refer to templates

(A01)

 

 

below.

 

 

 

 

 

 

 

 

4390–4419

IO Point Number 4

 

 

Register contents depend on IO Point Type. Refer to templates

(A02)

 

 

below.

 

 

 

 

 

 

 

 

4420–4449

IO Point Number 5

 

 

Register contents depend on IO Point Type. Refer to templates

(A03)

 

 

below.

 

 

 

 

 

 

 

 

4450–4479

IO Point Number 6

 

 

Register contents depend on IO Point Type. Refer to templates

(A04)

 

 

below.

 

 

 

 

 

 

 

 

4480–4509

IO Point Number 7

 

 

Register contents depend on IO Point Type. Refer to templates

(A05)

 

 

below.

 

 

 

 

 

 

 

 

4510–4539

IO Point Number 8

 

 

Register contents depend on IO Point Type. Refer to templates

(A06)

 

 

below.

 

 

 

 

 

 

 

 

4540–4569

IO Point Number 9

 

 

Register contents depend on IO Point Type. Refer to templates

(A07)

 

 

below.

 

 

 

 

 

 

 

 

4570–4599

IO Point Number 10

 

 

Register contents depend on IO Point Type. Refer to templates

(A08)

 

 

below.

 

 

 

 

 

 

 

 

4840–4869 ￿

IO Point Number 19

 

 

Register contents depend on IO Point Type. Refer to templates

(B01)

 

 

below.

4870–4899

IO Point Number 20

 

 

Register contents depend on IO Point Type. Refer to templates

(B02)

 

 

below.

 

 

 

 

 

 

 

 

4900–4929

IO Point Number 21

 

 

Register contents depend on IO Point Type. Refer to templates

(B03)

 

 

below.

 

 

 

 

 

 

 

 

These configuration registers require that you enter the setup mode to change the register’s contents. Issue command 9020 to enter setup

￿￿

mode and 9021 to exit setup mode. See “Using the Command Interface to Change Configuration Registers” on page 187 for instructions

 

 

on how to use the setup-mode commands.

 

 

 

© 2001 Schneider Electric All Rights Reserved

167

Page 179
Image 179