63230-300-212 Chapter4Metering Capa bilities
April 2001 Min/Max Values for Real-time Reading s
55
© 2001 Schneider Electric All Rights Reserved
The circuit monitorcan be set to one of two VAR sign conventions, thestandard IEEE or the ALT(CM1). Circuit monitors manufacturedbeforeMarch 2000default to the ALT VARsign convention.The Series 4000 CircuitMonitor defaultsto the IEEE VAR sign convention.Figure 42 illustrates theVARsign conventiondefined by IEEE and the default usedby previous modelcircuitm onitors(CM1). For instructions on changing the VAR signconvention, re fer to Advanced MeterSetupon page 34.Figure 42: Reactive PowerVAR sign convention

VARSign Conventions

Real

Power

In

Reactive

Power In

Quadrant
1
Quadrant
2
Quadrant
3Quadrant
4
Reverse Power Flow Normal Power Flow

Real

Power

In

Reactive

Power In

ALT (CM1) VAR Sign Convention IEEE/IEC VAR Sign Convention

(Series 4000 Circuit Monitor Default)

Quadrant
1
Quadrant
2
Quadrant
3Quadrant
4
Reverse Power Flow Normal Power Flow
watts negative (–)
vars negative (–)
power factor leading (+)
watts negative (–)
vars positive (+)
power factor lagging (–)
watts postive (+)
vars positive (+)
power factor leading (+)
watts positive (+)
vars negative (–)
power factor lagging (–)
watts negative (–)
vars positive (+)
power factor leading (+)
watts negative (–)
vars negative (–)
power factor lagging (–)
watts positive (+)
vars negative (–)
power factor leading (+)
watts positive (+)
vars positive (+)
power factor lagging (–)