Chapter 4—Metering Capabilities

 

 

 

 

 

 

63230-300-212

Energy Readings

 

 

 

 

 

 

 

 

April 2001

 

 

 

 

 

 

 

 

 

 

ENERGY READINGS

 

 

 

 

 

The circuit monitor calculates and stores accumulated energy values for real

 

 

 

 

 

 

 

and reactive energy (kWh and kVARh) both into and out of the load, and also

 

 

 

 

 

 

 

accumulates absolute apparent energy. Table 4–4lists the energy values the

 

 

 

 

 

 

 

circuit monitor can accumulate.

 

 

 

Table 4–4: Energy Readings

 

 

 

 

 

 

 

 

 

Energy Reading, 3-Phase

 

Reportable Range

 

Shown on the Display

 

 

 

 

 

 

 

Accumulated Energy

 

 

 

 

 

 

Real (Signed/Absolute)

 

-9,999,999,999,999,999 to

 

 

 

 

 

9,999,999,999,999,999 Wh

 

0000.000 kWh to 99,999.99 MWh and

 

 

 

 

 

 

 

 

 

 

 

Reactive (Signed/Absolute)

 

-9,999,999,999,999,999 to

 

0000.000 to 99,999.99 MVARh

 

 

 

9,999,999,999,999,999 VARh

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Real (In)

 

 

 

 

 

0 to 9,999,999,999,999,999 Wh

 

 

 

 

Real (Out)

 

 

 

 

0 to 9,999,999,999,999,999 Wh

 

 

 

 

Reactive (In)

 

 

 

0 to 9,999,999,999,999,999 VARh

 

0000.000 kWh to 99,999.99 MWh and

 

 

Reactive (Out)

 

 

0 to 9,999,999,999,999,999 VARh

 

0000.000 to 99,999.99 MVARh

 

 

Apparent

 

 

 

 

 

0 to 9,999,999,999,999,999 VAh

 

 

 

 

 

 

 

 

Accumulated Energy, Conditional

 

 

 

 

 

Real (In)

 

 

 

 

 

0 to 9,999,999,999,999,999 Wh

 

 

 

 

Real (Out)

 

 

 

 

0 to 9,999,999,999,999,999 Wh

 

Not shown on the display. Readings

 

 

 

 

 

 

 

are obtained only through the

 

 

Reactive (In)

 

 

 

0 to 9,999,999,999,999,999 VARh

 

 

 

 

 

 

 

communications link.

 

 

Reactive (Out)

 

 

0 to 9,999,999,999,999,999 VARh

 

 

 

 

Apparent

 

 

 

 

 

0 to 9,999,999,999,999,999 VAh

 

 

 

 

 

 

 

 

Accumulated Energy, Incremental

 

 

 

 

 

Real (In)

 

 

 

 

 

0 to 999,999,999,999 Wh

 

 

 

 

Real (Out)

 

 

 

 

0 to 999,999,999,999 Wh

 

0000.000 kWh to 99,999.99 MWh and

 

 

Reactive (In)

 

 

 

0 to 999,999,999,999 VARh

 

0000.000 to 99,999.99 MVARh

 

 

 

 

 

 

 

 

 

Reactive (Out)

 

 

0 to 999,999,999,999 VARh

 

 

 

 

Apparent

 

 

 

 

 

0 to 999,999,999,999 VAh

 

 

 

 

 

 

 

 

 

 

Reactive Energy

 

 

 

 

 

 

 

Quadrant 1

 

 

 

0 to 999,999,999,999 VARh

 

Not shown on the display. Readings

 

 

 

 

 

 

 

 

 

 

 

 

Quadrant 2

 

 

 

0 to 999,999,999,999 VARh

 

are obtained only through the

 

 

Quadrant 3

 

 

 

0 to 999,999,999,999 VARh

 

communications link.

 

 

 

 

 

 

 

 

 

Quadrant 4 ￿

 

 

0 to 999,999,999,999 VARh

 

 

 

 

 

 

 

 

 

Values can be displayed on the screen by creating custom quantities and custom displays.

 

 

 

￿

 

 

The circuit monitor can accumulate the energy values shown in Table 4–4in

 

 

 

 

 

one of two modes: signed or unsigned (absolute). In signed mode, the circuit

 

 

 

 

￿

￿

monitor considers the direction of power flow, allowing the magnitude of

 

 

 

 

 

accumulated energy to increase and decrease. In unsigned mode, the circuit

 

￿

 

￿

 

￿

monitor accumulates energy as a positive value, regardless of the direction

 

 

 

 

of power flow. In other words, the energy value increases, even during

 

 

 

 

 

 

reverse power flow. The default accumulation mode is unsigned.

 

 

 

 

 

 

You can view accumulated energy from the display. The resolution of the

 

 

 

 

 

 

energy value will automatically change through the range of 000.000 kWh to

 

 

 

 

 

 

000,000 MWh (000.000 to 000,000 MVARh), or it can be fixed.

 

 

 

 

 

 

See Appendix A—Abbreviated Register Listing on page 127 for the

 

 

 

 

 

 

contents of the registers.

 

 

64

 

 

 

 

 

 

 

 

© 2001 Schneider Electric All Rights Reserved

Page 76
Image 76
Schneider Electric 4000 manual Energy Readings, See Appendix A-Abbreviated Register Listing on page 127 for