Chapter 9—Disturbance Monitoring

63230-300-212

Using the Circuit Monitor with SMS to Perform Disturbance Monitoring

April 2001

 

 

USING THE CIRCUIT MONITOR WITH SMS TO PERFORM DISTURBANCE MONITORING

This section gives you an overview of the steps to set up the circuit monitor for disturbance monitoring. For detailed instructions, see the SMS online help. In SMS under Setup > Devices Routing, the Device Setup dialog box contains the tabs for setting up disturbance monitoring. After you have performed basic set up of the circuit monitor, perform three setup steps:

1.Define the storage space for the alarm log, waveform capture, and any forced data logs using the Onboard Files tab in SMS. This sets up the amount of circuit monitor memory that the logs and waveform capture will use.

Select a

Select how

data log

the log will

 

 

save data

Define the size of the waveform or event capture

Figure 9–3: Onboard Files tab

2.Associate an alarm with data logs and waveform/event captures using the Onboard Alarms/Events tab.

Define the alarm

Select data logs and/or waveform captures be associated with the alarm

Enable the alarm

Figure 9–4: Onboard Alarms/Events tab

3.In addition, you can set up a relay to operate upon an event using the I/O tab in SMS.

NOTE: For the I/O Extender, you must define the relay from the display before SMS can recognize it. See “Setting Up I/Os” on page 23 of this bulletin for instructions.

118

© 2001 Schneider Electric All Rights Reserved

Page 130
Image 130
Schneider Electric 4000 manual Onboard Files tab, Onboard Alarms/Events tab