Chapter 3—Operation 63230-300-212
Configuring the Circuit Monitor Using The Setup M enu April 2001
©200 1 Schneider Electric All Rights Reserved
16
Ethernet communicationsis available only if you havean opt ionalEthernet
CommunicationsCard (EC C) that fitsi ntoslot A on the top of the circuit
monitor.See Op tionCardson page 28 in Chapter 4—Installation of the
installationmanual for more information. Toset up the Ethernet
communicationsbetween the circuit monitor and the network, refer to
instructionbulletin no. 63230-304-200 provided with the ECC.
Toset up the metering within the circuit monitor,you must configure the
followingitems on the Meter setup screen for basic setup:
CT and PT ratios
System type
Frequency
The powerdemand method, interval and subinterval, andadvanced setup
optionsare also accessible from the MeterSetup menu, but are not required
forbasic setup if you are accepting thefactory defaults already defined in the
circuitmonitor. Follow these steps to set up the circuit monitor:
1. From the Main Menu, select Setup > Meter.
TheMeter setup screen displays. Table33 describes the options on this
menu.
2. Use the arrow buttons to scroll to the menu option you want to change.
3. Press the enter button to select the value.The value begins to blink. Use
the arrow buttonsto scroll through the available values.Then, press the
enter button to s elect the new value.
4. Use the arrow buttons to scroll throughthe other options on the menu, or
if you arefinished, press the menu button to save.
Parity Even, Od d, or
None
Parity at which the c ircuit monitor will
communicate.
Even
Table3–2: Optionsfor Communications Setup
EthernetCommunications Card (ECC)
Setup
Setting Up the Metering
Functions of the CircuitMonitor
Required for
basic setup
METER
Ø CT Primary 5
Ø CT Secondary 5
N CT Primary 5
N CT Secondary 5
PT Pri Scale x1
PT Primary 120
PT Secondary 120
Sys Type 3Ø4W3CT
Frequency (Hz) 60
Pwr Dmd Meth Slide
Pwr Dmd Int 15
Pwr Dmd Sub Int 1
Advanced