63230-300-212

Appendix A—Abbreviated Register Listing

April 2001

Register Listing

 

 

Table A–4:Abbreviated Register List for I/O Status

Register

Name

Units

Range

Description

Number

 

 

 

 

 

 

 

 

 

 

 

 

 

Bitmap indicting Demand System(s) to which input is assigned.

 

 

 

 

(Default = 0x003F)

 

 

 

 

Bit 00 = Power Demand

 

 

 

 

Bit 01 = Current Demand

 

 

 

 

Bit 02 = Voltage Demand

 

Demand Interval Sync

 

0x0000 to

Bit 03 = Input Metering Demand

Base + 10

Bit 04 = Generic Demand 1

System Assignments

0x003F

 

 

Bit 05 = Generic Demand 2

 

 

 

 

 

 

 

 

Only one Demand Sync Pulse per Demand System is allowed. If

 

 

 

 

the user attempts to configure more than one input for each system,

 

 

 

 

the lowest IO Point Number will take precedence. The

 

 

 

 

corresponding bits of the other points will be set to 0.

 

 

 

 

 

Base + 11

Digital Input Options

0x0000 to

Bitmap of digital Input Options. (Default = 0)

0x0001

Bit 00 = Debounce time (0 = 5msec, 1 = 50msec)

 

 

 

 

 

 

 

 

 

 

 

 

Bitmap indicting metering pulse channel(s) to which input is

 

 

 

 

assigned. (Default = 0)

 

 

 

 

Bit 00 = Channel 1

 

 

 

 

Bit 01 = Channel 2

 

 

 

 

Bit 02 = Channel 3

Base + 14

Metering Pulse

0x0000 to

Bit 03 = Channel 4

Channel Assignments

0x03FF

Bit 04 = Channel 5

 

 

 

 

 

 

Bit 05 = Channel 6

 

 

 

 

Bit 06 = Channel 7

 

 

 

 

Bit 07 = Channel 8

 

 

 

 

Bit 08 = Channel 9

 

 

 

 

Bit 09 = Channel 10

 

 

 

 

 

Base + 15

Metering Pulse

1.0

1- 32,767

Pulse weight associated with the change of state of the input. Used

Weight, Demand

for demand metering. (Default = 1)

 

 

 

 

 

 

 

 

Base + 16

Metering Pulse Scale

1.0

-3 to 3

Pulse weight scale factor (power of 10) to apply to metering pulse

Factor, Demand

weight. Used for demand metering. (Default = 0)

 

 

 

 

 

 

 

 

Base + 17

Metering Pulse

1.0

1- 32,767

Pulse weight associated with the change of state of the input. Used

Weight, Consumption

for consumption metering. (Default = 1)

 

 

 

 

 

 

 

 

Base + 18￿

Metering Pulse Scale

1.0

-3 to 3

Pulse weight scale factor (power of 10) to apply to metering pulse

 

Factor, Consumption

 

 

weight. Used for consumption metering. (Default = 0)

 

 

 

 

IO Point Diagnostic Bitmap:

Base + 22

IO Point Diagnostic

0x0000 to

0 = OK, 1 = Error

Bitmap

0xFFFF

Bit 00 = IO Point diagnostic summary

 

 

 

 

 

 

Bit 01 = Configuration invalid to default value used

 

 

 

 

 

Base + 25

Digital Input On/Off

0 to 1

digital input Off/On status: 0 = Off, 1 = On

Status

 

 

 

 

 

 

 

 

 

Base + 26

Count

0 to

Number of times input has transitioned from Off to On

99,999,999

 

 

 

 

 

 

 

 

 

Base + 28

On Time

Seconds

0 to

Duration that digital input has been On

99,999,999

 

 

 

 

 

 

 

 

 

Digital Output Template

 

 

 

These configuration registers require that you enter the setup mode to change the register’s contents. Issue command 9020 to enter setup

￿￿

mode and 9021 to exit setup mode. See “Using the Command Interface to Change Configuration Registers” on page 187 for instructions

 

 

on how to use the setup-mode commands.

 

 

 

© 2001 Schneider Electric All Rights Reserved

169

Page 181
Image 181
Schneider Electric 4000 manual Digital Output Template, 169