Schneider Electric 4000 manual Accessories and Options for the Circuit Monitor, Introduction April

Models: 4000

1 216
Download 216 pages 20.25 Kb
Page 15
Image 15

63230-300-212

Chapter 1—Introduction

April 2001

What is the Circuit Monitor?

 

 

Accessories and Options for the Circuit Monitor

The circuit monitor has a modular design to maximize its usability. In addition to the main meter, the circuit monitor has plug-on modules and accessories, including:

Current/voltage module (CVM). A standard part of the circuit monitor is the current/voltage module where all metering data acquisition occurs.

Remote display. The optional remote 4-line display is available with a back-lit liquid crystal display (LCD) or a vacuum fluorescent display (VFD). The VFD model includes an infrared port that can be used to communicate directly with the circuit monitor from a laptop and can be used to download firmware, which keeps the circuit monitor up to date with the latest system enhancements.

I / O Extender. The I/O extender, located on the side of the circuit monitor, enables you to “plug in” up to 8 industry-standard inputs and outputs. Several preconfigured combinations are available, or you can create a custom configuration.

Digital I /O Card. You can further expand the I/O capabilities of the circuit monitor by adding a digital I/O card (4 inputs and 4 outputs). This card fits into one of the option slots on the top of the circuit monitor.

Ethernet Communications Card. The Ethernet communications card provides an Ethernet port that accepts a 100 Mbps fiber optic cable or a 10 /100 Mbps UTP and provides an RS-485 master port to extend the circuit monitor communications options. This card is easily installed into option slot A on the top of the circuit monitor.

Table 1–2lists the circuit monitor parts and accessories and their associated instruction bulletins.

Table 1–2: Circuit Monitor Parts, Accessories, and Custom Cables

Description

Part Number

Document Number

 

 

 

Circuit Monitor

CM4000

63230-300-200

 

 

 

Current/ Voltage Module

CVM

63230-301-200

 

 

 

VFD Display with infrared (IR) port and proximity sensor

CMDVF

63230-305-200

 

 

LCD Display

CMDLC

 

 

 

 

Optical Communications Interface (for use with the VFD display only)

OCIVF

63230-306-200

 

 

 

I/O Extender Module

 

 

 

 

 

with no preinstalled I/ Os, accepts up to 8 individual I/O modules with a

IOX

 

maximum of 4 analog I/Os

 

 

 

 

 

 

with 4 digital inputs (32￿Vdc), 2 digital outputs (60 Vdc),

IOX2411

63230-302-200

1 analog output (4–20 mA), and 1 analog input (0–5 Vdc)

 

 

with 4 analog inputs (4–20 mA) and 4 digital inputs (120 Vac)

IOX0404

 

 

 

 

with 8 digital inputs (120 Vac)

IOX08

 

 

 

 

Digital I/O Card

 

 

Field installable with 4 digital inputs (120 Vac), 3 (10 A) relay outputs (120Vac),

IOC44

63230-303-200

1 pulse output (KYZ)

 

 

 

 

 

Ethernet Communications Card with

ECC21

63230-304-200

100 Mbps fiber or 10/100 Mbps UTP Ethernet port and 1 RS-485 master port

 

 

 

 

 

Optical Communications Interface

OCIVG

63230-306-200

 

 

 

Memory Expansion Kit (16 MB and 32 MB kits)

CM4MEM16M

63230-300-205

CM4MEM32M

 

 

 

 

 

For parts list of individual inputs and outputs, see Table 5–1 on page 70.

 

 