Appendix A—Abbreviated Register Listing

63230-300-212

Register Listing

April 2001

 

 

Table A–3:Abbreviated Register List

Register

Description

Scale

Units

Register Range

Number

Factor

 

 

 

 

 

 

 

 

1601

Maximum THD/thd Current, Phase B

0.10%

0 to 32,767

 

 

 

 

 

1602

Maximum THD/thd Current, Phase C

0.10%

0 to 32,767

 

 

 

 

 

1603

Maximum THD/thd Current, Phase N

0.10%

0 to 32,767

 

 

 

 

 

1604

Maximum THD/thd Current, Ground

0.10%

0 to 32,767

 

 

 

 

 

1607

Maximum THD/thd Voltage, Phase A-N

0.10%

0 to 32,767

 

 

 

 

 

1608

Maximum THD/thd Voltage, Phase B-N

0.10%

0 to 32,767

 

 

 

 

 

1609

Maximum THD/thd Voltage, Phase C-N

0.10%

0 to 32,767

 

 

 

 

 

1610

Maximum THD/thd Voltage, Phase N-G

0.10%

0 to 32,767 ￿

 

 

 

 

 

1611

Maximum THD/thd Voltage, Phase A-B

0.10%

0 to 32,767

 

 

 

 

 

1612

Maximum THD/thd Voltage, Phase B-C

0.10%

0 to 32,767

 

 

 

 

 

1613

Maximum THD/thd Voltage, Phase C-A

0.10%

0 to 32,767

 

 

 

 

 

1618

Maximum Current K-Factor, Phase A

0.10

0 to 10,000

 

 

 

 

 

1619

Maximum Current K-Factor, Phase B

0.10

0 to 10,000

 

 

 

 

 

1620

Maximum Current K-Factor, Phase C

0.10

0 to 10,000

 

 

 

 

 

1621

Maximum Crest Factor, Current, Phase A

0.01

0 to 10,000

 

 

 

 

 

1622

Maximum Crest Factor, Current, Phase B

0.01

0 to 10,000

 

 

 

 

 

1623

Maximum Crest Factor, Current, Phase C

0.01

0 to 10,000

 

 

 

 

 

1624

Maximum Crest Factor, Current, Neutral

0.01

0 to 10,000

 

 

 

 

 

1625

Maximum Crest Factor, Voltage A-N/A-B

0.01

0 to 10,000 ￿

 

 

 

 

 

1626

Maximum Crest Factor, Voltage B-N/B-C

0.01

0 to 10,000

 

 

 

 

 

1627

Maximum Crest Factor, Voltage C-N/C-A

0.01

0 to 10,000

 

 

 

 

 

1630

Maximum Current Fundamental RMS Magnitude, Phase A

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1631

Maximum Current Fundamental Coincident Angle, Phase A

0.1 °

0 to 3,599

 

 

 

 

 

1632

Maximum Current Fundamental RMS Magnitude, Phase B

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1633

Maximum Current Fundamental Coincident Angle, Phase B

0.1 °

0 to 3,599

 

 

 

 

 

1634

Maximum Current Fundamental RMS Magnitude, Phase C

A

Amps/Scale

0 to 32,767

 

 

 

 

 

1635

Maximum Current Fundamental Coincident Angle, Phase C

0.1 °

0 to 3,599

 

 

 

 

 

1636

Maximum Current Fundamental RMS Magnitude, Neutral

B

Amps/Scale

0 to 32,767

 

 

 

 

 

1637

Maximum Current Fundamental Coincident Angle, Neutral

0.1 °

0 to 3,599

 

 

 

 

 

1638

Maximum Current Fundamental RMS Magnitude, Ground

C

Amps/Scale

0 to 32,767 ￿

 

 

 

 

 

1639

Maximum Current Fundamental Coincident Angle, Ground

0.1 °

0 to 3,599 ￿

 

 

 

 

 

1644

Maximum Voltage Fundamental RMS Magnitude, A-N/A-B

D

Volts/Scale

0 to 32,767

 

 

 

 

 

1645

Maximum Voltage Fundamental Coincident Angle, A-N/A-B

0.1 °

0 to 3,599

 

 

 

 

 

1646

Maximum Voltage Fundamental RMS Magnitude, B-N/B-C

D

Volts/Scale

0 to 32,767

 

 

 

 

 

1647

Maximum Voltage Fundamental Coincident Angle, B-N/B-C

0.1 °

0 to 3,599

 

 

 

 

 

1648

Maximum Voltage Fundamental RMS Magnitude, C-N/C-A

D

Volts/Scale

0 to 32,767

 

 

 

 

 

See “How Power Factor is Stored in the Register” on page 128.

The alternate storage method for power factor (PF) is useful for outputting PF on analog outputs. The PF value is stored as a positive value between 0 and 2, centered around 1 (unity). A value of 0 lagging maps to 0; -0.999 maps to 0.999;0.999 leading maps to 1.001; and 0 leading maps to 2. The alternate PF is also stored with a scale factor 0.001.

These configuration registers require that you enter the setup mode to change the register’s contents. Issue command 9020 to enter setup mode and 9021 to exit setup mode. See “Using the Command Interface to Change Configuration Registers” on page 187 for instructions on

￿how to use the setup-mode commands.

Quantity available for 4-wire system only. Value set to -32,768 if not available.

142

© 2001 Schneider Electric All Rights Reserved

Page 154