Chapter 3—Operation

63230-300-212

Configuring the Circuit Monitor Using The Setup Menu

April 2001

 

 

The I/O Extender Setup menu displays.

I/O EXTENDER SETUP

Select Modules

Configure Modules

5.Select the Select Modules menu option. The IOX Select Modules menu displays.

IOX SELECT MODULES

IOX-08

IOX-0404

IOX-2411

Custom

6.If you have the IOX-08, IOX-0404, or IOX-2411, select the option you have installed. A pound sign (#) appears next to the option to indicate that the circuit monitor has recognized the module. If you installed individual custom I/Os, select Custom on the IOX Select Modules menu.

The Custom Extender menu displays.

CUSTOM

 

 

Position 1

DI120AC

 

 

Position 2

AI420

 

Position 3

DI120AC

 

Position 4

AI420

 

Position 5

DI120AC

 

Position 6

AI420

 

Position 7

DI120AC

 

Position 8

AI420

7.Select the position in which the I/O is installed. Then, select which I/O module is located in that position using the arrow keys to scroll through the available I/Os. The individual I/Os are described in Table 3–6.

Table 3–6: I/O Descriptions

I/O Name

Description

 

 

 

Digital I/Os

 

 

 

 

DI32DC

32 Vdc input (0.2ms turn on) polarized

 

 

 

DI120AC

120

Vac input

 

 

 

DO120AC

120

Vac output

 

 

 

DI240AC

240

Vac input

 

 

DO60DC

60 Vdc output

 

 

 

DO200DC

200

Vdc output

 

 

 

24

© 2001 Schneider Electric All Rights Reserved

Page 36