Chapter 10—Maintenance and Troubleshooting

63230-300-212

Troubleshooting

April 2001

 

 

Table 10–1: Troubleshooting

Cannot communicate with circuit

Circuit monitor address is incorrect.

Check to see that the circuit monitor is correctly

monitor from a remote personal

 

addressed. See “RS-485,RS-232, and Infrared Port

computer.

 

Communications Setup” on page 15 for instructions.

 

 

 

 

Circuit monitor baud rate is incorrect.

Verify that the baud rate of the circuit monitor matches the

 

 

baud rate of all other devices on its communications link.

 

 

See “RS-485,RS-232, and Infrared Port Communications

 

 

Setup” on page 15 for instructions.

 

 

 

 

Communications lines are improperly

Verify the circuit monitor communications connections.

 

connected.

Refer to Chapter 6—Communications Connections of the

 

 

installation manual for instructions.

 

 

 

 

Communications lines are improperly

Check to see that a multipoint communications terminator

 

terminated.

is properly installed. See “Terminating the

 

 

Communications Link” on page 67 of the installation

 

 

manual for instructions.

 

 

 

 

Incorrect route statement to circuit monitor.

Check the route statement. Refer to the SMS online help

 

 

for instructions on defining route statements.

 

 

 

126

© 2001 Schneider Electric All Rights Reserved

Page 138
Image 138
Schneider Electric 4000 manual Maintenance and Troubleshooting 63230-300-212 April, 126