Chapter 4—Metering Capabilities 63230-300-212
Demand Readings April 2001
©200 1 Schneider Electric All Rights Reserved
56
The circuitmonitor provides a variety of demand readings, including
coincidentreadings and predicted demands. Table4–3liststheavailable
demand readingsand their reportable ranges.
Tabl e 4–3: Demand Readings
Demand Readings Report able Range
Demand Current, Per-Phase, 3ØAverage,Neutral
Last Complete Interval 0 to 3 2,767 A
Peak 0 to 32,767 A
Demand Voltage, L–N, L–L, Per-phase, Average, N-G
Last Complete Interval 0 to 1 200 kV
Minimum 0 to 1200 kV
Peak 0to1200kV
AveragePowerFactor (True),3ØTo t a l
Last Complete Interval –0.010to 1.000 to + 0.010
Coincidentwith kW Peak –0.010 to 1.000 to +0.010
Coincidentwith kVARPeak –0.010 to 1.000 to + 0.010
Coincidentwith kVA Peak –0. 010 to 1.000 to +0.010
Demand Real Power,3ØTot a l
Last Complete Interval 0to ± 3276.70 MW
Predicted 0 to± 3276.70 MW
Peak 0 to ± 3276.70 MW
CoincidentkVA Demand 0 to ± 3276.70 MVA
CoincidentkVAR Demand 0 to ± 3276.70MVAR
Demand Reactive Power,3ØTo t a l
Last Complete Interval 0to ± 3276.70 MVAR
Predicted 0 to± 3276.70 MVAR
Peak 0 to ± 3276.70 MVAR
CoincidentkVA Demand 0 to ± 3276.70 MVA
CoincidentkW Demand 0 to ± 3276.70 MW
Demand Apparent Power,3ØTo tal
Last Complete Interval 0to ± 3276.70 MVA
Predicted 0 to± 3276.70 MVA
Peak 0 to ± 3276.70 MVA
CoincidentkW Demand 0 to ± 3276.70 MW
CoincidentkVAR Demand 0 to ± 3276.70MVAR
DEMAND READINGS