63230-300-212

Appendix A—Abbreviated Register Listing

April 2001

Register Listing

 

 

Table A–3:Abbreviated Register List

Register

Description

Scale

Units

Register Range

Number

Factor

 

 

 

 

 

 

 

 

Metering Configuration

 

 

 

 

 

 

 

 

 

Metering System Type

 

 

 

 

System Connection

 

 

 

 

30 = 3PH3W2CT

 

 

 

3200

31 = 3PH3W3CT

30,31, 40,41,42,43

40 = 3PH4W3CT (default)

 

 

 

 

 

41 = 3PH4W4CT

 

 

 

 

42 = 3PH4W3CT2PT

 

 

 

 

43 = 3PH4W4CT2PT

 

 

 

 

 

 

 

 

3201

CT Ratio, Phase Primary

Amps

1 to 32,767, Default = 5

 

 

 

 

 

3202

CT Ratio, Phase Secondary

Amps

1, 5, Default = 5

 

 

 

 

 

3203

CT Ratio, Neutral Primary

Amps

1 to 32,767, Default = 5

 

 

 

 

 

3204

CT Ratio, Neutral Secondary

Amps

1, 5, Default = 5

 

 

 

 

 

3205

PT Ratio, Phase Primary

Volts/Scale

1 to 32,767, Default = 120

 

 

 

 

 

3206

PT Ratio, Phase Primary Scale Factor

-1 to 2, Default = 0

-1 = Direct Connect

 

 

 

 

 

 

 

 

 

3207

PT Ratio, Phase Secondary

Volts

100, 110, 115, 120;

Default = 120

 

 

 

 

 

 

 

 

 

3208

Nominal System Frequency

Hertz

50,60,400; Default = 60

 

 

 

 

 

3209

Scale A to Phase Amps

-2 to 1, Default = 0

 

 

 

 

 

3210

Scale B to Neutral Amps

-2 to 1, Default = 0

 

 

 

 

 

3211

Scale C to Ground Amps

-2 to 1, Default = 0

 

 

 

 

 

3212

Scale D to Phase Volts

-1 to 2, Default = 0

 

 

 

 

 

3213

Scale E to Neutral Volts

-1 to 2, Default = -1

 

 

 

 

 

3214

Scale F to Power

-3 to 3, Default = 0

 

 

 

 

 

3216 ￿

Scale H to Transient Voltages

0 to 3, Default = 1

 

 

 

 

 

See “How Power Factor is Stored in the Register” on page 128.

The alternate storage method for power factor (PF) is useful for outputting PF on analog outputs. The PF value is stored as a positive value between 0 and 2, centered around 1 (unity). A value of 0 lagging maps to 0; -0.999 maps to 0.999;0.999 leading maps to 1.001; and 0 leading maps to 2. The alternate PF is also stored with a scale factor 0.001.

These configuration registers require that you enter the setup mode to change the register’s contents. Issue command 9020 to enter setup mode and 9021 to exit setup mode. See “Using the Command Interface to Change Configuration Registers” on page 187 for instructions on

￿how to use the setup-mode commands.

Quantity available for 4-wire system only. Value set to -32,768 if not available.

© 2001 Schneider Electric All Rights Reserved

159

Page 171
Image 171
Schneider Electric 4000 manual Metering Configuration, 159