63230-300-212 Chapter6Alarms
April 2001 Set point-Controlled Relay Functions
89
© 2001 Schneider Electric All Rights Reserved
Thissection describes some common motor management functionsto which
the followinginformation applies:
Valuesthat are too large to fit into the display may require scalefactors.
For more informationon scale factors, refer to Changing ScaleFactors
on page 191 in Appendix BUsingthe Command Interface.
Relayscan be configured as normal, latched, ortimed. See Relay Output
OperatingModeson page 75 in Chapter 5Input/Output Capabilities
for more infor mation.
When the alarm occurs,the circuit monitor operates any specified relays.
There are two waysto release relays that are in latched mode:
Issue a commandto de-energize a relay. See Appendix BUsing
the Command Interface on page 181 forinstructions on using the
command interface,or
Acknowledgethe alarm in the high priority log to release the relays
from latchedmode. From the main menu of the display,select View
Alarms> High Priority Log to view and acknowledge unacknowledged
alarms. See Viewing Alarmson page 41 for detailed instructions.
The list that followsshows the types of alarms available for some common
motor managementfunctions:
NOTE: Voltagebase alarm setpoints depend on your system configuration.Alarm setpoi nts for 3-wire systems are V L-Lvalues while 4-wire systems areVL-N values.
Undervoltage:
Pickup and dropoutsetpoints are entered in volts. The per-phase
undervoltagealarm occurs when the per-phase voltage is equal to or below
the pickupsetpoint long enough to satisfy the specified pickup delay(in
seconds). The undervoltagealarm clears when the phase voltage remains
abovethe dropout setpoint for the specified dropout delay period.
Overvoltage:
Pickupand dropout setpoints are enteredin volts. The per-phase overvoltage
alarm occurs when the per-phasevoltage is equal to or above the pickup
setpoint longenough to satisfy the specified pickup delay (in seconds).The
overvoltagealarm clears when the phase voltage remainsbelow the dropout
setpoint forthe specified dropout delay period.
Unbalance Current:
Pickupand dropout setpoints are entered in tenths of percent, based on the
percentage differencebetween each phase current with respect to the
averageof all phase currents. For example,enter an unbalance of 7% as 70.
The unbalance currentalarm occurs when the phase current deviates from
theaverage of the phase currents, bythe percentage pickup setpoint,for the
specifiedpi ckupdelay. The alarm clears when the percentagedifference
betweenthe phase current and the average of all phases remainsbelow the
dropout setpointfor the specified dropout delay period.
Typesof Setpoint-Controlled
Relay Functions