Chapter 3—Operation 63230-300-212
Configuring the Circuit Monitor Using The Setup M enu April 2001
©200 1 Schneider Electric All Rights Reserved
36
Table3–10: Options for Advanced Meter Setup
Option AvailableValues Selection Description Default
PhaseRotation ABC or CBA Sett hephase rotation to matchthe system. ABC
Incr Energy Int 01440 Set incremental energy inter val in minutes. The interval must be evenly di visible into
24hours.
60
THDMeth THD(%Fund)or
thd(%RMS)
Setthe calculation fortotal harmonic distortion.See Power Analys is Valueson page
66for a detailed description.
THD
VARSign IEEE/IECor
ALT(CM1)
Set the VARs ign convention. See VAR SignConventionsonpage 55 fora discussion
about VAR sign convention.
Standard
LockEnergy Reset Y or N Lock the resetof the accumulated energy.If set to Y(yes), the Energy optionon the
Reset menu will be locked so that the val ue cannot be reset from the disp lay,even if a
passwordhasbeen set up forthe Reset option.See Resetting Min/Max,Demand, and
Energy Valueson page37 for more information.
N
Lock Pk Dmd Reset Yor N Lock the res et of peak demand. If set to Y (yes), the Dem and option on the Reset
menu will be locked so that the value can not be reset from the display, even if a
passwordhasbeen set up forthe Reset option.See Resetting Min/Max,Demand, and
Energy Valueson page37 for more information.
N
LockM/M Reset Y or N Lock thereset of the min/max values.If set to Y (yes),the Min/Max option on the Reset
menu will be locked so that the value can not be reset from the display, even if a
passwordhasbeen set up forthe Reset option.See Resetting Min/Max,Demand, and
Energy Valueson page37 for more information.
N