Appendix AAbbreviated Regist er Listing 63230-300-212
Register Listing April 2001
©200 1 Schneider Electric All Rights Reserved
162
3314 Average/Min/Max Log Channel # 14 Meter Register
0 = No calculationfor this channel ——
0,1100 to 2999; Default =
1171Displacement Power
Factor,Total
3315 Average/Min/Max Log Channel # 15 Meter Register
0 = No calculationfor this channel ——
0,1100 to 2999; Default =
1207THD/thd VoltagePhase
A-N
3316 Average/Min/Max Log Channel # 16 Meter Register
0 = No calculationfor this channel ——
0,1100 to 2999; Default =
1208THD/thd VoltagePhase
B-N
3317 Average/Min/Max Log Channel # 17 Meter Register
0 = No calculationfor this channel ——
0,1100 to 2999; Default =
1209THD/thd VoltagePhase
C-N
3318 Average/Min/Max Log Channel # 18 Meter Register
0 = No calculationfor this channel ——
0,1100 to 2999; Default =
1211THD/thd VoltagePhase
A-B
3319 Average/Min/Max Log Channel # 19 Meter Register
0 = No calculationfor this channel ——
0,1100 to 2999; Default =
1212THD/thd VoltagePhase
B-C)
3320 Average/Min/Max Log Channel # 20 Meter Register
0 = No calculationfor this channel ——
0,1100 to 2999; Default =
1213THD/thd VoltagePhase
C-A
3321 Average/Min/Max Log Channel # 21 Meter Register
0 = No calculationfor this channel ——
0,1100 to 2999; Default =
2150Last Demand, Real
Power, 3-Phase Total
3322 Average/Min/Max Log Chann el #22Meter Registe r
0 = No calculationfor this channel ——
0,1100 to 2999; Default =
2165Last Demand, Reactive
Power, 3-Phase Total
3323 Average/Min/Max Log Channel # 23 Meter Register
0 = No calculationfor this channel ——
0,1100 to 2999; Default =
2180Last Demand,Apparent
Power, 3-Phase Total
3324 Average/Min/Max Log Channel # 24 Meter Register
0 = No calculationfor this channel ——0, 1100 to 2999; Default = 0
3325 Average/Min/Max Log Channel # 25 Meter Register
0 = No calculationfor this channel ——0, 1100 to 2999; Default = 0
3350
DiscreteInput Point Assignmentto Discrete Input Status
Bitmap Bit 00
IO Point Number for Discrete Input t oi nclude in Discrete Input
StatusBitmap: Bit 00.
0 =none, default = 3 (Dig InA-S1)
——0to66
3351
DiscreteInput Point Assignmentto Discrete Input Status
Bitmap Bit 01
IO Point Number for Discrete Input t oi nclude in Discrete Input
StatusBitmap: Bit 01.
0 =none, default = 4 (Dig InA-S2)
——0to66
Tabl e A3:AbbreviatedRegister List
Register
Number Description Scale
Factor Units Register Range
See How Power Factor is Stored in t he Registeron page 128.
Thealternate storage methodfor power factor(PF) is useful for outputtingPF on analog outputs.The PF valueis stored as a positivevalue
between0 and 2,centered around1 (unity). A valueof 0 lagging mapsto 0; -0.999 mapsto 0.999;0.999 leadingmaps to 1.001;and 0 leading
mapsto 2. The alternate PF is alsostored with a scale factor0.001.
Theseconfiguration registersrequire that youenter the setup mode to change the registerscontents. Issuecommand 9020 to enter setup
mode and 9021 to exit setup mode. See Us ing the Command Interface to Cha nge Configuration Regist erson page 187 for instruction s on
howtousethesetup-modecommands.
Quantity available for 4- wire system only. Value set to - 32,768 if not available.