Chapter 5—Input/Output Capabilities

63230-300-212

Demand Synch Pulse Input

April 2001

 

 

DEMAND SYNCH PULSE INPUT

You can configure the circuit monitor to accept a demand synch pulse from

 

an external source such as another demand meter. By accepting demand

 

synch pulses through a digital input, the circuit monitor can make its demand

 

interval “window” match the other meter’s demand interval “window.” The

 

circuit monitor does this by “watching” the digital input for a pulse from the

 

other demand meter. When it sees a pulse, it starts a new demand interval

 

and calculates the demand for the preceding interval. The circuit monitor

 

then uses the same time interval as the other meter for each demand

 

calculation. Figure 5–1illustrates this point. See “Synchronized Demand” on

 

page 59 in Chapter 4—Metering Capabilities for more about demand

 

calculations.

 

When in demand synch pulse operating mode, the circuit monitor will not

 

start or stop a demand interval without a pulse. The maximum allowable time

 

between pulses is 60 minutes. If 66 minutes (110% of the demand interval)

 

pass before a synch pulse is received, the circuit monitor throws out the

 

demand calculations and begins a new calculation when the next pulse is

 

received. Once in synch with the billing meter, the circuit monitor can be used

 

to verify peak demand charges.

 

Important facts about the circuit monitor’s demand synch feature are listed

 

below:

Any installed digital input can be set to accept a demand synch pulse.

Each system can choose whether to use an external synch pulse, but only one demand synch pulse can be brought into the meter for each demand system. One input can be used to synchronize any combination of the demand systems.

The demand synch feature can be set up from SMS. See the SMS online help for instructions on device set up of the circuit monitor.

Normal Demand Mode

External Synch Pulse Demand Timing

Billing Meter

Billing Meter

Demand Timing

Demand Timing

 

Utility Meter

 

Synch Pulse

Circuit Monitor

Circuit Monitor

Demand Timing

Demand Timing

 

(Slaved to Master)

Figure 5–1: Demand synch pulse timing

72

© 2001 Schneider Electric All Rights Reserved

Page 84
Image 84