63230-300-212 April 2001

Priorities

Alarm Levels

Chapter 6—Alarms

About Alarms

Each alarm also has a priority level. Use the priorities to distinguish between events that require immediate action and those that do not require action.

High priority—if a high priority alarm occurs, the display informs you in two ways: the LED on the display flashes until you acknowledge the alarm and a message displays while the alarm is active.

Medium priority—if a medium priority alarm occurs, the LED flashes and a message displays only while the alarm is active. Once the alarm becomes inactive, the LED stops flashing.

Low priority—if a low priority alarm occurs, the LED on the display flashes only while the alarm is active. No alarm message is displayed.

No priority—if an alarm is setup with no priority, no visible representation will appear on the display. Alarms with no priority are not entered in the Alarm Log. See Chapter 7—Loggingfor alarm logging information.

If multiple alarms with different priorities are active at the same time, the display shows the alarm message for the last alarm that occurred. For instructions on setting up alarms from the circuit monitor display, see “Setting Up and Editing Alarms” on page 21.

From the display or SMS, multiple alarms can be set up for one particular quantity (parameter) to create alarm “levels”. You can take different actions depending on the severity of the alarm.

For example, you could set up two alarms for kW Demand. A default alarm already exists for kW Demand (no. 26 in the alarm list), but you could create another custom alarm for kW Demand, selecting different pickup points for it. The custom kW Demand alarm, once created, will appear in the standard alarm list. For illustration purposes, let’s set the default kW Demand alarm to 120 kW and the new custom alarm to 150 kW. One alarm named kW Demand ; the other kW Demand 150kW as shown in Figure 6–3.Note that if you choose to set up two alarms for the same quantity, use slightly different names to distinguish which alarm is active. The display can hold up to 15 characters for each name. You can create up to 10 alarm levels for each quantity.

kW Demand

150

 

 

 

 

 

Alarm #43 Pick Up

 

Alarm # 43 Drop Out

 

 

 

140

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

130

 

 

 

Alarm #26 Pick Up

 

 

 

Alarm #26 Drop Out

 

 

 

 

 

 

120

 

 

 

 

 

 

 

 

 

 

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Time

 

 

 

Demand OK Approaching

Peak Demand

Below Peak Demand OK

Peak Demand

Exceeded

Demand

kW Demand (default)

 

kW Demand 150kW (custom)

Alarm #26 kW Demand with

Alarm #43 kW Demand with

pickup of 120 kWd, medium priority

pickup of 150 kWd, high priority

Figure 6–3: Two alarms set up for the same quantity with different pickup and dropout set points

© 2001 Schneider Electric All Rights Reserved

87

Page 99
Image 99
Schneider Electric 4000 manual Priorities Alarm Levels, Alarms About Alarms