63230-300-212 Chapter3—Operation
April 2001 Configuring the Circuit Monitor Using Th eS etup Menu
25
© 2001 Schneider Electric All Rights Reserved
8. Pr essthe menu button until Save Changes? Noflashes on the display.
Select Yeswith the arrow button,then press the enter button to savethe
changes.
After selectingthe I/O modules used with your circuit monitor, you can
configurethe I/O modules. Followthe steps below to configurethe inputs and
outputs forthe I/O module you selected.
1. From the Main Menu, select Setup.
The passwordprompt displays
2. Select your password. The default passwordis 0.
The Setup menu displays.
3. Select I/O.
TheI/OSetupmenudisplays.
4. Select the I/O option that you have installed.In this example, we selected
the I/O Extender.
DO240AC 240Vac output
AnalogI/Os
AI05 0to5Vdcanaloginput
AI420 4to 20 mA analog input
AO420 4to 20 mA analog output
Table3–6: I/O Descriptions
I/O Name Description
Configuring I/O Modules
SETUP
Date & Time
Display
Communications
Meter
Alarm
I/O
Passwords
I/O
KYZ
I/O Extender