Chapter 5—Input/Output Capabilities

 

63230-300-212

Analog Outputs

 

April 2001

 

 

Analog Output Example

Figure 5–5illustrates the relationship between the output range of current (in

 

milliamperes) and the upper and lower limit of power usage (real power in

 

kW). In this example, the analog output has been configured as follows:

 

Register Number:

1143 (Real Power, 3-Phase Total)

 

Lower Limit:

100 kW

 

Upper Limit:

500 kW

Table 5–3shows the output current at various register readings.

Table 5–3: Sample register readings for analog output

Register Reading (kW)

Output Current (mA)

 

 

50

4

 

 

100

4

 

 

200

8

 

 

250

10

 

 

500

20

 

 

550

20

 

 

Output

Current

( Maximum )

Output Current 20 mA

(OutputMinimumCurrent) 4 mA

Real Power, 3Ø Total (from register 1143)

100 kW

500 kW

( LowerLimit )

( UpperLimit )

Figure 5–5: Analog output example