63230-300-212

Appendix A—Abbreviated Register Listing

April 2001

Register Listing

 

 

Table A–3:Abbreviated Register List

Register

Description

Scale

Units

Register Range

Number

Factor

 

 

 

 

 

 

 

 

1193

Auxiliary Analog Input Value, User-Selected Input 4

Refer to Analog Input

-32,767 to 32,767

Setup

 

 

 

 

 

 

 

 

 

1194

Auxiliary Analog Input Value, User-Selected Input 5

Refer to Analog Input

-32,767 to 32,767

Setup

 

 

 

 

 

 

 

 

 

1195

Auxiliary Analog Input Value, User-Selected Input 6

Refer to Analog Input

-32,767 to 32,767

Setup

 

 

 

 

 

 

 

 

 

1196

Auxiliary Analog Input Value, User-Selected Input 7

Refer to Analog Input

-32,767 to 32,767

Setup

 

 

 

 

 

 

 

 

 

1197

Auxiliary Analog Input Value, User-Selected Input 8

Refer to Analog Input

-32,767 to 32,767

Setup

 

 

 

 

 

 

 

 

 

1198

Auxiliary Analog Input Value, User-Selected Input 9

Refer to Analog Input

-32,767 to 32,767

Setup

 

 

 

 

 

 

 

 

 

1199

Auxiliary Analog Input Value, User-Selected Input 10

Refer to Analog Input

-32,767 to 32,767

Setup

 

 

 

 

 

 

 

 

 

Power Quality

 

 

 

 

 

 

 

 

 

1200

THD/thd Current, Phase A

0.10%

0 to 32,767

 

 

 

 

 

1201

THD/thd Current, Phase B

0.10%

0 to 32,767

 

 

 

 

 

1202

THD/thd Current, Phase C

0.10%

0 to 32,767

 

 

 

 

 

1203

THD/thd Current, Neutral

0.10%

0 to 32,767

 

 

 

 

 

1204

THD/thd Current, Ground

0.10%

0 to 32,767

 

 

 

 

 

1207

THD/thd Voltage, Phase A-N

0.10%

0 to 32,767

 

 

 

 

 

1208

THD/thd Voltage, Phase B-N

0.10%

0 to 32,767

 

 

 

 

 

1209

THD/thd Voltage, Phase C-N

0.10%

0 to 32,767

 

 

 

 

 

1210

THD/thd Voltage, Phase N-G

0.10%

0 to 32,767 ￿

 

 

 

 

 

1211

THD/thd Voltage, Phase A-B

0.10%

0 to 32,767

 

 

 

 

 

1212

THD/thd Voltage, Phase B-C

0.10%

0 to 32,767

 

 

 

 

 

1213

THD/thd Voltage, Phase C-A

0.10%

0 to 32,767

 

 

 

 

 

1218

K-Factor, Current, Phase A

0.10

0 to 10,000

 

 

 

 

 

1219

K-Factor, Current, Phase B

0.10

0 to 10,000

 

 

 

 

 

1220

K-Factor, Current, Phase C

0.10

0 to 10,000

 

 

 

 

 

1221

Crest Factor, Current, Phase A

0.01

0 to 10,000

 

 

 

 

 

1222

Crest Factor, Current, Phase B

0.01

0 to 10,000

 

 

 

 

 

1223

Crest Factor, Current, Phase C

0.01

0 to 10,000

 

 

 

 

 

1224

Crest Factor, Current, Neutral

0.01

0 to 10,000

 

 

 

 

 

1225

Crest Factor, Voltage, A-N/A-B

0.01

0 to 10,000

 

 

 

 

 

1226

Crest Factor, Voltage, B-N/B-C

0.01

0 to 10,000

 

 

 

 

 

1227

Crest Factor, Voltage, C-N/C-A

0.01

0 to 10,000

 

 

 

 

 

1230

Current Fundamental RMS Magnitude, Phase A

A

Amps/Scale

0 to 32,767

 

 

 

 

 

See “How Power Factor is Stored in the Register” on page 128.

The alternate storage method for power factor (PF) is useful for outputting PF on analog outputs. The PF value is stored as a positive value between 0 and 2, centered around 1 (unity). A value of 0 lagging maps to 0; -0.999 maps to 0.999;0.999 leading maps to 1.001; and 0 leading maps to 2. The alternate PF is also stored with a scale factor 0.001.

These configuration registers require that you enter the setup mode to change the register’s contents. Issue command 9020 to enter setup mode and 9021 to exit setup mode. See “Using the Command Interface to Change Configuration Registers” on page 187 for instructions on

￿how to use the setup-mode commands.

Quantity available for 4-wire system only. Value set to -32,768 if not available.