Bryant manual BASE UNIT DIMENSIONS - 582A048-060

Models: 582A

1 24
Download 24 pages 11.98 Kb
Page 8
Image 8
BASE UNIT DIMENSIONS – 582A048-060

BASE UNIT DIMENSIONS – 582A048-060

REQ'D CLEARANCES FOR OPERATION AND SERVICING. in. (mm)

Evaporator coil access side

. .

.

. . . . . . . . . 36

(914)

Power entry side (except for NEC requirements) .

. . . . . . . . 36 (914)

Unit top

. .

.

. . . . . . . . . 36

(914)

Side opposite ducts

. . . . . . . . 36

(914)

Duct panel

. . . . . . . 12 (304.8)*

*Minimum distances: If unit is placed less than 12 in. (304.8 mm) from wall system, then the system performance may be compromised.

 

 

LEGEND

CG

Center of Gravity

COND

Condenser

EVAP

Evaporator

NEC

National Electrical Code

REQ'D

Required

NOTE: Dimensions are in mm [in.]

REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm)

Top of unit . . . . . . . . . . . . . . . . . . . . . . . . . 14 (355.6) Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . 2 (50.8) Side opposite ducts . . . . . . . . . . . . . . . . . . . . . 14 (355.6) Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . 0.50 (12.7) Flue panel . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914.4)

NEC REQ'D CLEARANCES. in. (mm)

 

 

 

 

 

Between units, power entry side

.

.

. .

. 42

(1066.8)

Unit and ungrounded surfaces, power entry side . . .

 

.

. .

. . . 36 (914)

Unit and block or concrete walls and other grounded

 

 

 

 

 

surfaces, control box side

.

.

. .

. 42

(1066.8)

FLUE HOOD

UNIT

ELECTRICAL

UNIT WEIGHT

 

CENTER OF GRAVITY

 

 

 

in. [mm]

 

582A

CHARACTERISTICS

 

 

 

 

 

lb

kg

X

 

 

Y

 

Z

 

 

 

 

 

048090/115/130

208-230/1/60, 208/230-3-60, 460-3-60

415

188.6

22 [558.5]

 

16

[406.4]

 

17 [432.0]

060090/115/130

208/230-1-60, 208/230-3-60, 460-3-60

450

204.5

22 [558.5]

 

16

[406.4]

 

17 [432.0]

 

 

 

 

 

 

 

 

 

 

8

Page 8
Image 8
Bryant manual BASE UNIT DIMENSIONS - 582A048-060