BASE UNIT DIMENSIONS – 582A048-060
REQ'D CLEARANCES FOR OPERATION AND SERVICING. in. (mm)
Evaporator coil access side | . . | . | . . . . . . . . . 36 | (914) | |
Power entry side (except for NEC requirements) . | . . . . . . . . 36 (914) | ||||
Unit top | . . | . | . . . . . . . . . 36 | (914) | |
Side opposite ducts | . . . . . . . . 36 | (914) | |||
Duct panel | . . . . . . . 12 (304.8)* |
*Minimum distances: If unit is placed less than 12 in. (304.8 mm) from wall system, then the system performance may be compromised.
|
| LEGEND |
CG | – | Center of Gravity |
COND | – | Condenser |
EVAP | – | Evaporator |
NEC | – | National Electrical Code |
REQ'D | – | Required |
NOTE: Dimensions are in mm [in.]
REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm)
Top of unit . . . . . . . . . . . . . . . . . . . . . . . . . 14 (355.6) Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . 2 (50.8) Side opposite ducts . . . . . . . . . . . . . . . . . . . . . 14 (355.6) Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . 0.50 (12.7) Flue panel . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914.4)
NEC REQ'D CLEARANCES. in. (mm) |
|
|
|
|
|
Between units, power entry side | . | . | . . | . 42 | (1066.8) |
Unit and ungrounded surfaces, power entry side . . . |
| . | . . | . . . 36 (914) | |
Unit and block or concrete walls and other grounded |
|
|
|
|
|
surfaces, control box side | . | . | . . | . 42 | (1066.8) |
FLUE HOOD
UNIT | ELECTRICAL | UNIT WEIGHT |
| CENTER OF GRAVITY |
| ||||
|
| in. [mm] |
| ||||||
582A | CHARACTERISTICS |
|
|
|
|
| |||
lb | kg | X |
|
| Y |
| Z | ||
|
|
|
|
| |||||
048090/115/130 | 415 | 188.6 | 22 [558.5] |
| 16 | [406.4] |
| 17 [432.0] | |
060090/115/130 | 450 | 204.5 | 22 [558.5] |
| 16 | [406.4] |
| 17 [432.0] | |
|
|
|
|
|
|
|
|
|
|
8