GUIDE SPECIFICATIONS (cont)
K.Electrical Requirements:
All unit power wiring shall enter the unit cabinet at a single location.
L.Motors:
1.Compressor motors shall be of the
2.All fan motors shall have permanently lubricated bear- ings, and inherent, automatic reset, thermal overload protection.
3.
1.Louvered Grille:
Wire grille shall be standard on all units. Louvered grille shall be available as a
2.Coil Options:
Shall include
3.Economizer:
a.Economizer controls capable of providing free cooling using outside air.
b.Equipped with low leakage dampers not to exceed 3% leakage, at 1.0 in. wg pressure differential.
c.Spring return motor shuts off outdoor damper on power failure.
4.Flat Roof Curb:
Curbs shall have seal strip and a wood nailer for flashing and shall be installed per manufacturer’s instructions.
5.Manual Outdoor Air Damper:
Package shall consist of damper, birdscreen, and rainhood which can be preset to admit outdoor air for
7.
Shall be complete with all required hardware to con- vert to liquid propane (LP) operation at 3.5 in. wg manifold pressure.
8.Low Ambient Package:
Shall consist of a
motor operation, which shall allow unit to operate down to 0° F outdoor ambient temperature.
9.Filter Rack Kit:
Shall provide filter mounting for downflow applications.
10.Controls Upgrade Kit:
Shall provide high and low pressure safety protection.
11.
Shall have the ability to convert the supply and return openings from rectangular to round.
12.Compressor Protection:
13.Duct Conversion Kit:
Shall enable conversion of a
14.Crankcase Heater:
Shall provide
15.
Shall consist of natural gas orifices to compensate for gas heat operation at 2001 to 4500 ft above sea level.
16.Low NOx :
Shall provide NOx reduction to values below 40 nanograms/joule to meet California emission requirements as shipped from the factory.
6. Thermostat: | 17. Compressor Hard Start Kit: |
|
To provide for
Shall provide additional starting torque for single- phase compressors.
Heating & Cooling Systems
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS