NOMINAL TONS

STANDARD CFM

NET COOLING

SEER†

SOUND RATINGS**

CAPACITIES (Btuh)

(Bels)

 

 

 

 

018040

11/2

600

18,000

10.0

7.5

024040

2

800

24,600

10.0

7.5

024060

 

 

 

 

 

030040

21/2

1000

28,800

10.0

7.5

030060

 

 

 

 

 

036060

3

1200

34,400

10.0

8.0

036090

 

 

 

 

 

042060

31/2

1400

42,000

10.0

8.0

042090

 

 

 

 

 

048090

 

 

 

 

 

048115

4

1600

46,500

10.0

8.0

048130

 

 

 

 

 

060090

 

 

 

 

 

060115

5

2000

60,000

10.0

8.0

060130

 

 

 

 

 

 

 

LEGEND

Bels

Sound Levels (1 bel = 10 decibels)

db

Dry Bulb

SEER

Seasonal Energy Efficiency Ratio

wb

Wet Bulb

*Air Conditioning & Refrigeration Institute.

†Rated in accordance with U.S. Government DOE (Department of Energy) test procedures and/or ARI Standard 210/89.

**Tested in accordance with ARI Standard 270-89 (not listed in ARI).

NOTES:

1.Ratings are net values, reflecting the effects of circulating fan

heat. Ratings are based on:

Cooling Standard: 80°F db, 67°F wb indoor entering-air tem- perature and 95°F db outdoor entering-air temperature.

2.Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.

HEATING CAPACITIES AND EFFICIENCIES

UNIT 582A

HEATING INPUT

OUTPUT CAPACITY

TEMPERATURE

AFUE (%)

(Btuh)

(Btuh)

RISE RANGE (°F)

 

 

018040

 

31,000

 

79.9

024040

40,000

31,000

20-50

80.1

030040

 

31,000

 

80.1

024060

 

46,000

35-65

78.4

030060

60,000

46,000

35-65

78.4

036060

46,000

25-55

78.7

 

042060

 

47,000

25-55

78.7

036090

 

71,000

 

79.9

042090

90,000

71,000

40-70

79.9

048090

70,000

78.6

 

 

060090

 

70,000

 

78.6

048115

115,000

92,000

50-80

81.1

060115

 

 

 

 

048130

130,000

104,000

50-80

80.3

060130

103,000

 

 

 

LEGEND

AFUE – Annual Fuel Utilization Efficiency

NOTE: Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.