Bryant manual PERFORMANCE DATA cont NET COOLING CAPACITIES cont, 582A060

Models: 582A

1 24
Download 24 pages 11.98 Kb
Page 13
Image 13

PERFORMANCE DATA (cont)

NET COOLING CAPACITIES (cont)

582A060

 

 

 

 

 

 

 

 

 

 

 

 

 

TEMP (F)

 

 

 

 

 

 

EVAPORATOR AIR – CFM/BF

 

 

 

 

OUTDOOR-AIR

 

 

 

1750/0.039

 

 

2000/0.053

 

 

2250/0.079

 

 

 

ENTERING

 

 

 

 

 

 

Evaporator Air – Ewb (F)

 

 

 

 

CONDENSER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

 

67

 

72

62

67

72

62

67

72

 

 

 

 

 

 

 

 

 

 

TC

 

53.9

 

61.5

 

69.3

56.1

63.6

71.1

58.0

65.2

72.4

 

85

 

SHC

 

48.8

 

41.4

 

33.4

53.7

45.2

35.7

58.0

48.8

37.9

 

 

 

kW

 

6.12

 

6.33

 

6.52

6.21

6.38

6.57

6.25

6.42

6.62

 

 

 

TC

 

50.7

 

58.1

 

65.8

52.8

60.0

67.5

55.2

61.4

68.8

 

95

 

SHC

 

47.4

 

40.1

 

32.2

51.9

43.9

34.5

55.2

47.4

36.7

 

 

 

kW

 

6.44

 

6.69

 

6.89

6.53

6.74

6.94

6.63

6.78

6.98

 

 

 

TC

 

47.2

 

54.4

 

62.2

49.6

56.1

63.7

52.2

57.5

64.9

 

105

 

SHC

 

45.7

 

38.7

 

30.9

49.6

42.5

33.3

52.2

46.0

35.5

 

 

 

kW

 

6.75

 

7.07

 

7.27

6.87

7.11

7.33

7.01

7.15

7.37

 

 

 

TC

 

43.7

 

50.4

 

58.2

46.6

52.0

59.6

49.1

53.3

60.7

 

115

 

SHC

 

43.7

 

37.2

 

29.6

46.6

40.9

32.0

49.1

44.4

34.2

 

 

 

kW

 

7.08

 

7.43

 

7.67

7.24

7.50

7.73

7.38

7.53

7.77

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

Ewb

Entering Wet-Bulb

 

 

 

 

 

 

 

 

 

 

 

kW

Total Unit Power Input

 

 

 

 

 

 

 

 

 

 

 

SHC

Sensible Heat Capacity (1000 Btuh)

 

 

 

 

 

 

 

 

 

TC

Total Capacity (1000 Btuh) (net)

 

 

 

 

 

 

 

 

 

NOTES:

1.Ratings are net; they account for the effects of the evaporator-fan motor power and heat.

2.Direct interpolation is permissible. Do not extrapolate.

3.The following formulas may be used:

t ldb = t edb2

sensible capacity (Btuh)

1.10 x cfm

tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb )

hlwb = hewb2

total capacity (Btuh)

4.5 x cfm

Where: hewb = Enthalpy of air entering evaporator coil

13

Page 13
Image 13