Appendix A—Abbreviated Register Listing

April 2001

Register Listing

 

 

Table A–3:Abbreviated Register List

Register

Description

Scale

Units

Register Range

Number

Factor

 

 

 

 

 

 

 

 

2420 to 2439

Generic Channel #2

 

 

 

Same as registers 2400 to 2419 except for Channel #2

 

 

 

 

 

 

 

 

 

 

 

 

2440 to 2459

Generic Channel #3

 

 

 

Same as registers 2400 to 2419 except for Channel #3

 

 

 

 

 

 

 

 

 

 

 

 

2460 to 2479

Generic Channel #4

 

 

 

Same as registers 2400 to 2419 except for Channel #4

 

 

 

 

 

 

 

 

 

 

 

 

2480 to 2499

Generic Channel #5

 

 

 

Same as registers 2400 to 2419 except for Channel #5

 

 

 

 

 

 

 

 

 

 

 

 

2500 to 2519

Generic Channel #6

 

 

 

Same as registers 2400 to 2419 except for Channel #6

 

 

 

 

 

 

 

 

 

 

 

 

2520 to 2539

Generic Channel #7

 

 

 

Same as registers 2400 to 2419 except for Channel #7

 

 

 

 

 

 

 

 

 

 

 

 

2540 to 2559

Generic Channel #8

 

 

 

Same as registers 2400 to 2419 except for Channel #8

 

 

 

 

 

 

 

 

 

 

 

 

2560 to 2579

Generic Channel #9

 

 

 

Same as registers 2400 to 2419 except for Channel #9

 

 

 

 

 

 

 

 

 

 

 

 

2580 to 2599

Generic Channel #10

 

 

 

Same as registers 2400 to 2419 except for Channel #10

 

 

 

 

 

 

 

 

 

 

 

 

2600 to 2619

Generic Channel #11

 

 

 

Same as registers 2400 to 2419 except for Channel #11

 

 

 

 

 

 

 

 

 

 

 

 

See “How Power Factor is Stored in the Register” on page 128.

The alternate storage method for power factor (PF) is useful for outputting PF on analog outputs. The PF value is stored as a positive value between 0 and 2, centered around 1 (unity). A value of 0 lagging maps to 0; -0.999 maps to 0.999;0.999 leading maps to 1.001; and 0 leading maps to 2. The alternate PF is also stored with a scale factor 0.001.

These configuration registers require that you enter the setup mode to change the register’s contents. Issue command 9020 to enter setup mode and 9021 to exit setup mode. See “Using the Command Interface to Change Configuration Registers” on page 187 for instructions on

￿how to use the setup-mode commands.

Quantity available for 4-wire system only. Value set to -32,768 if not available.