Appendix AAbbreviated Regist er Listing 63230-300-212
Register Listing April 2001
©200 1 Schneider Electric All Rights Reserved
136
1325 MinimumVoltage,B-N D Volts/Scale 0 to 32,767
1326 MinimumVoltage,C-N D Volts/Scale 0 to 32,767
1327 MinimumVoltage,N-G E Volts/Scale 0 to 32,767
1328 MinimumVoltage,L-N Average D Volts/Scale 0 to 32,767
1329 MinimumVoltage Unbalance,A-B 0.10% -1,000to 1,000
1330 MinimumVoltage Unbalance,B-C ���0.10% -1,000to 1,000
1331 MinimumVoltage Unbalance,C-A 0.10% -1,000to 1,000
1332 MinimumVoltage Unbalance,Max L-L 0.10% -1,000to 1,000
1333 MinimumVoltage Unbalance,A-N 0.10% -1,000to 1,000
1334 MinimumVoltage Unbalance,B-N 0.10% -1,000to 1,000
1335 MinimumVoltage Unbalance,C-N 0.10% -1,000 to 1,000
1336 MinimumVoltage Unbalance,Max L-N 0.10% -1,000 to 1,000
1340 MinimumReal Power,Phase A F kW/Scale -32,767 to 32,767
1341 MinimumReal Power,Phase B F kW/Scale -32,767 to 32,767
1342 MinimumReal Power,Phase C F kW/Scale -32,767 to 32,767
1343 Minimum Rea l Power,Total F kW/Scale -32,767 to 32,767
1344 MinimumReactive Power,Phase A F kVAr/Scale -32,767to 32,767
1345 MinimumReactive Power,Phase B F kVAr/Scale -32,767to 32,767
1346 MinimumReactive Power,Phase C F kVAr/Scale - 32,767to 32,767
1347 MinimumReactive Power,Total F kVAr/Scale -32,767to 32,767
1348 Minimum Ap parent Power, Phase A F kVA/Scale -32,767 to 32,767
1349 MinimumApparent Power,Phase B F kVA/Scale -32,767 to 32,767
1350 MinimumApparent Power,Phase C F kVA/Scale -32,767to 32,767
1351 MinimumApparent Power,Total F kVA/Scale -32,767 to 32,767
1360 MinimumTrue PowerFactor, PhaseA 0. 001 1,000 -100 to 100
1361 MinimumTrue PowerFactor, PhaseB 0. 001 1,000 -100 to 100
1362 MinimumTrue PowerFactor, PhaseC 0.001 1 ,000 -100 to 100
1363 MinimumTrue PowerFactor, Total 0.001 1,0 00 -100 to 100
1364 MinimumAlternate TruePower Factor,Phase A 0.001 0 to 2,0 00
1365 MinimumAlternate TruePower Factor,Phase B 0.001 0 to 2,0 00
1366 MinimumAlternate TruePower Factor,Phase C 0.001 0 to 2,000
1367 MinimumAlternate TruePower Factor,Total 0.001 0 to 2,000
1368 MinimumDisplacement PowerFactor,Phase A 0.001 1 ,000 -100 to 100
1369 MinimumDisplacement PowerFactor,Phase B 0.001 1 ,000 -100 to 100
1370 MinimumDisplacement PowerFactor,Phase C 0.001 1,000 - 100 to 100
1371 MinimumDisplacement PowerFactor,Total 0.001 1,000 -100 to 1 00
Tabl e A3:AbbreviatedRegister List
Register
Number Description Scale
Factor Units Register Range
See How Power Factor is Stored in t he Registeron page 128.
Thealternate storage methodfor power factor(PF) is useful for outputtingPF on analog outputs.The PF valueis stored as a positivevalue
between0 and 2,centered around1 (unity). A valueof 0 lagging mapsto 0; -0.999 mapsto 0.999;0.999 leadingmaps to 1.001;and 0 leading
mapsto 2. The alternate PF is alsostored with a scale factor0.001.
Theseconfiguration registersrequire that youenter the setup mode to change the registerscontents. Issuecommand 9020 to enter setup
mode and 9021 to exit setup mode. See Us ing the Command Interface to Cha nge Configuration Regist erson page 187 for instruction s on
howtousethesetup-modecommands.
Quantity available for 4- wire system only. Value set to - 32,768 if not available.