63230-300-212 AppendixAAbbreviatedR egisterListing
April 2001 Registe r Listing
161
© 2001 Schneider Electric All Rights Reserved
3241
Harmonic Magnitude For mat
0 = % of Fundamental(default)
1=%ofRMS
——0to1
3242 HarmonicRefresh Interval Sec onds 1 0 to 60, Default = 30
3243 Time Rema ining Until Harm onic Refresh Sec onds 10 to 60
3270 to 3273 Minimum/Maximum Rese tD ate/Time See Template See Template
3274to 3277 AccumulatedEnergyReset Date/Time See Template SeeTemplate
3278 to 3281 Conditional Energy Reset Date/T ime See Template SeeTemplate
3282 to 3285 Incremental Energy Reset Date/T ime SeeTemplate See Template
3286 to 3289 Input Metering Accumulation R eset Date/Time See Template See Template
3290to 3293 AccumulatedEnergyPreset Date/Time See Template See Template
3299
Average/Min/Max Log Number of Data Items
Numberof Quantities forwhich Average/Min/Maxcalculations
aremade and logged.
125
3300 Average/Min/Max Log I nterval
Must be evenly divisible into 1440. Minutes 1 to 1440, Default= 60
3301 Average/Min/MaxLogChannel #1 Meter Register
0= No calculation for thischannel ——
0,1100 to 2999; Default =
1100Current, Phase A
3302 Average/Min/MaxLogChannel #2 Meter Register
0= No calculation for thischannel ——
0,1100 to 2999; Default =
1101Current, Phase B
3303 Average/Min/MaxLogChannel #3 Meter Register
0= No calculation for thischannel ——
0,1100 to 2999; Default =
1102Current, Phase C
3304 Average/Min/MaxLogChannel #4 Meter Register
0= No calculation for thischannel ——
0,1100 to 2999; Default =
1103Current, Neutral
3305 Average/Min/MaxLogChannel #5 Meter Register
0= No calculation for thischannel ——
0,1100 to 2999; Default =
1104 Current, Ground
3306 Average/Min/MaxLogChannel #6 Meter Register
0= No calculation for thischannel ——
0,1100 to 2999; Default =
1120Voltage, A-B
3307 Average/Min/MaxLogChannel #7 Meter Register
0= No calculation for thischannel ——
0,1100 to 2999; Default =
1121Voltage B-C
3308 Average/Min/MaxLogChannel #8 Meter Register
0= No calculation for thischannel ——
0,1100 to 2999; Default =
1122Voltage C-A
3309 Average/Min/MaxLogChannel #9 Meter Register
0= No calculation for thischannel ——
0,1100 to 2999; Default =
1127Voltage N-G
3310 Average/Min/MaxLogChannel #10 Meter Register
0= No calculation for thischannel ——
0,1100 to 2999; Default =
1143Real Power, Total
3311 Average/Min/MaxLogChannel #11 Meter Register
0= No calculation for thischannel ——
0,1100 to 2999; Default =
1147Reactive Power,Total
3312 Average/Min/MaxLogChannel #12 Meter Register
0= No calculation for thischannel ——
0,1100 to 2999; Default =
1151Apparent Power,Total
3313 Average/Min/MaxLogChannel #13 Meter Register
0= No calculation for thischannel ——
0,1100 to 2999; Default =
1163True PowerFactor,Total
Tabl e A3:AbbreviatedRegister List
Register
Number Description Scale
Factor Units Regist er Range
See HowPower Factoris Stored in the Registeronpage 128.
Thealternate storage methodfor power factor(PF) is useful for outputtingPF on analog outputs.The PF value isstored as a positive value
between 0 and 2, centered around 1 (un ity). A value of 0 lagging maps to 0; -0.99 9m aps to 0.999;0.999 leading m aps to 1.001; and 0 leading
mapsto 2. The alternate PF is alsostored with a scale factor0.001.
These configuration r egisters require th at you enter the setup mo de to change the regi sters contents. Issue command 9020 t o enter setup
modeand 9021 to exit setup mode.S ee Usingthe Command Interfaceto Change ConfigurationRegistersonpage 187 for instructions on
howto use the setup-mode commands.
Quantity available for 4-w ire system only. Value set to -32, 768 if not available.