63

Troubleshooting Tips

The table below lists typical symptoms and the corresponding solution(s).

 

Symptom/condition

Probable Cause

Solution

 

 

 

 

Is the frequency command source

Make sure the parameter

 

 

 

 

A001 parameter setting correct?

setting A001 is correct

 

 

 

 

Is the Run command source A002

Make sure the parameter

 

 

 

 

parameter setting correct?

setting A002 is correct

 

 

 

 

Is power being supplied to terminals

Check terminals [L1], [L2],

 

 

 

 

[L1], [L2], and [L3/N]? If so, the

and [L3/N], then [U/T1],

 

 

 

 

POWER lamp should be ON.

[V/T2], and [W/T3].

 

 

 

 

 

Turn ON the power supply or

 

 

 

 

 

check fuses.

 

 

 

 

Is there an error code E X X

Press the Func. key and

 

 

 

The inverter

displayed?

determine the error type.

 

 

 

 

Eliminate the error cause,

 

 

 

outputs [U], [V],

 

 

 

 

 

then clear the error (Reset).

 

 

 

[W] are not

 

 

 

 

Are the signals to the intelligent

Verify the terminal functions

 

 

 

supplying

 

 

 

input terminals correct?

for C001–C005 are correct.

 

 

 

voltage

 

 

 

Is the Run Command active?

Turn ON Run Command

 

 

 

 

 

 

The motor

 

Is the [FW] terminal (or [RV])

enable.

 

 

 

connected to [PCS] (via switch, etc.)

Supply 24V to [FW] or [RV]

 

 

will not run

 

 

 

 

 

terminal, if configured.

 

 

 

 

 

 

 

 

 

Has the frequency setting for F001

Set the parameter for F001 to

 

 

 

 

been set greater than zero?

a safe, non-zero value.

 

 

 

 

Are the control circuit terminals

If the potentiometer is the

 

 

 

 

[H], [O], and [L] connected to the

frequency setting source,

 

 

 

 

potentiometer?

verify voltage at [O] > 0V.

 

 

 

 

Is the RS (reset) function or FRS

Turn OFF the command(s)

 

 

 

 

(free-run stop) function ON?

 

 

 

 

Inverter

Is the motor load too heavy?

Reduce the load, and test the

 

 

 

outputs [U],

 

motor independently.

 

 

 

[V], [W] are

 

 

 

 

 

supplying

 

 

 

 

 

voltage.

 

 

 

 

 

The optional

Are the operational settings

Check the operator type

 

 

 

remote

between the remote operator and

setting.

 

 

 

operator is

the inverter unit correct?

 

 

 

 

used (SRW).

 

 

 

 

 

 

Are the connections of output

Make connections according to

 

 

 

 

terminals [U/T1], [V/T2], and [W/T3]

the phase sequence of the

 

 

 

 

correct?

motor. In general:

 

 

The direction of the motor is

Is the phase sequence of the motor

FWD = U-V-W, and REV=U-

 

 

reversed

forward or reverse with respect to

W-V.

 

 

[U/T1], [V/T2], and [W/T3]?

 

 

 

 

 

 

 

 

 

 

Are the control terminals [FW] and

Use terminal [FW] for

 

 

 

 

[RV] wired correctly?

forward, and [RV] for reverse.

 

 

 

 

Is parameter F004 properly set?

Set motor direction in F004.

 

 

 

 

 

 

 

Troubleshooting and Maintenance

Page 206
Image 206
Hitachi X200 Series instruction manual Troubleshooting Tips, Symptom/condition Probable Cause Solution