Control Logic Signal Specifications

The control logic connectors are located just behind the front housing cover. The relay contacts are just to the left of the logic connectors. Connector labeling is shown below.

Analog Analog output inputs

Relay contacts

 

 

 

 

 

 

 

 

AL2

AL1

AL0

 

 

 

 

 

 

 

 

 

Logic

 

 

 

 

 

 

 

 

 

Logic inputs

 

 

 

output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operations and Monitoring

AM H O OI L 5 4 3 2 1 L PLC P24 CM2 11

Short bar : default position (Source logic)

Terminal Name

Description

 

Ratings

[P24]

+24V for logic inputs

24VDC, 30mA. (do not short to terminal L)

[PLC]

Intelligent input common

Factory set: Source type for –FE and –HE

 

 

models (connecting [P24] to [1]~[5] makes

 

 

each input ON). To change to sink type,

 

 

remove the short wire between [PLC] and

 

 

[L], and connect it between [P24] and [L]. In

 

 

this case, connecting [L] to [1]~[5] makes

 

 

each input ON.

[1], [2], [3], [4], [5]

Discrete logic inputs

27VDC max. (use PLC or an external

 

 

supply referenced to terminal L)

[L] (right) *1

GND for logic inputs

Sum of input [1]~[5] currents (return)

[11]

Discrete logic output

50mA max. ON state current,

 

 

27 VDC max. OFF state voltage

[CM2]

GND for logic output

100 mA: [11] current return

[AM]

Analog voltage output

0~10VDC 1mA maximum

[L] (left) *2

GND for analog signals

Sum of [OI], [O], and [H] currents (return)

[OI]

Analog input, current

4 to 19.6 mA range, 20 mA nominal,

 

 

input impedance 250

[O]

Analog input, voltage

0 to 9.8 VDC range, 10 VDC nominal,

 

 

input impedance 10 k

[H]

+10V analog reference

10VDC nominal, 10mA max.

[AL0]

Relay common contact

250VAC, 2.5A (R load) max.

[AL1] *3

Relay contact, normally open

250VAC, 0.2A (I load, P.F.=0.4) max.

[AL2] *3

Relay contact, normally closed

100VAC,

10mA min.

 

 

30VDC,

3.0A (R load) max.

 

 

30VDC,

0.7A (I load, P.F.=0.4) max.

 

 

5VDC, 100mA min.

Note 1: The two terminals [L] are electrically connected together inside the inverter.

Note 2: We recommend using [L] logic GND (to the right) for logic input circuits and [L] analog GND (to the left) for analog I/O circuits.

Note 3: Default relay N.O./N.C. configuration is reversed. See page 4-35.