“B” Function

Run

Defaults

 

 

 

Func.

Name /

 

Description

Mode -FE -FU

Units

 

 

 

 

Code

SRW Display

Edit (EU)

 

(USA)

 

 

 

B001

Selection of automatic restart

Select inverter restart method,

 

00

 

00

 

 

 

 

 

mode

 

Four option codes:

 

 

 

 

 

 

 

 

 

 

 

 

 

00Alarm output after trip, no

 

 

 

 

 

 

 

 

 

 

 

 

 

automatic restart

 

 

 

 

 

 

 

 

 

 

 

 

 

01Restart at 0Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

02Resume operation after

 

 

 

 

 

 

 

 

 

 

 

 

 

frequency pull-in

 

 

 

 

 

 

 

 

 

 

 

 

 

03Resume previous freq. after

 

 

 

 

 

 

 

 

 

 

 

 

 

freq. pull-in, then decelerate

 

 

 

 

 

 

 

 

 

 

 

 

 

to stop and display trip info

 

 

 

 

 

 

 

 

 

 

 

IPS POWR

ALM

 

 

 

 

 

 

 

 

 

 

 

B002

Allowable under-voltage

The amount of time a power

 

1.0

 

1.0

 

sec.

 

 

 

 

power failure time

 

input under-voltage can occur

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

without tripping the power

 

 

 

 

 

 

 

 

ConfiguringDrive Parameters

 

 

 

 

failure alarm. Range is 0.3 to 25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

sec. If under-voltage exists longer

 

 

 

 

 

 

 

 

 

 

 

 

 

than this time, the inverter trips,

 

 

 

 

 

 

 

 

 

 

 

 

 

even if the restart mode is

 

 

 

 

 

 

 

 

 

 

 

IPS Time

0001.0s

selected.

 

 

 

 

 

 

 

 

 

 

B003

Retry wait time before motor

Time delay after under-voltage

 

1.0

 

1.0

 

sec.

 

 

 

 

restart

 

condition goes away, before the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

inverter runs motor again.

 

 

 

 

 

 

 

 

 

 

 

IPS Wait

0001.0s

Range is 0.3 to 100 seconds.

 

 

 

 

 

 

 

 

 

 

B004

Instantaneous power failure /

Two option codes:

 

00

 

00

 

 

 

 

 

under-voltage trip alarm

00Disable

 

 

 

 

 

 

 

 

 

 

 

enable

 

01Enable

 

 

 

 

 

 

 

 

 

 

 

IPS TRIP

OFF

 

 

 

 

 

 

 

 

 

 

 

B005

Number of restarts on power

Two option codes:

 

00

 

00

 

 

 

 

 

failure / under-voltage trip

00Restart 16 times

 

 

 

 

 

 

 

 

 

 

 

events

 

01Always restart

 

 

 

 

 

 

 

 

 

 

 

IPS RETRY

16

 

 

 

 

 

 

 

 

 

 

 

B011

Start freq to be used in case

Three option codes:

 

00

 

00

 

 

 

 

 

of freq pull-in restart

00freq at previous shutoff

 

 

 

 

 

 

 

 

 

 

 

 

 

01start from max. Hz

 

 

 

 

 

 

 

 

 

 

 

FSch Md

CUTOFF

02start from set frequency

 

 

 

 

 

 

 

 

 

 

B029

Deceleration rate of freq pull-

Sets the deceleration rate when

 

0.5

 

0.5

 

sec.

 

 

 

 

in restart setting

 

frequency pull-in restart, range is

 

 

 

 

 

 

 

 

 

 

 

FSch CNS

0000.5s

0.1 to 3000.0, resolution 0.1

 

 

 

 

 

 

 

 

 

 

B030

Current level of

frequency

Sets the current level of

 

Rated

A

 

 

 

 

pull-in restart setting

frequency pull-in restart, range is

 

current

 

 

 

 

 

 

 

 

0.2*inverter rated current to

 

 

 

 

 

 

 

 

 

 

 

 

 

2.0*inverter rated current,

 

 

 

 

 

 

 

 

 

 

 

 

 

resolution 0.1

 

 

 

 

 

 

 

 

 

 

 

FSch LVL

002.60A

 

 

 

 

 

 

 

 

 