Configuring Drive Parameters

345

B130, B131: Over-voltage LAD Stop Enable

 

 

/ Level – The over-voltage LADSTOP

B130 = 01 OV LADSTOP = Enable

function monitors the DC bus voltage and

 

 

actively changes the output frequency

DC bus

 

profile to maintain the DC bus voltage

voltage

 

within settable limits. Although “LAD”

B131

 

refers to “linear acceleration / deceleration”,

 

 

the inverter only “STOPs” the deceleration

 

 

slope so that regenerative voltage will not

0

t

cause the DC bus to rise enough to cause an

 

 

over-voltage trip event. Note that

Output

Stops decel

acceleration is not affected.

frequency

The graph at right shows an inverter

 

 

output profile that starts deceleration to a

 

 

stop. At two different points during the

 

Resumes decel

deceleration, regenerative voltage elevates

 

0

t

the DC bus level, exceeding the LADSTOP

 

Set dec time (F003)

threshold set by B131.

 

Actual dec time

 

 

When the Over-voltage LADSTOP feature is enabled by B130 = 01, the inverter stops the deceleration ramp in each case until the DC bus level is again less than the threshold value.

When using the Over-voltage LADSTOP feature, please note the following:

When the over-voltage LADSTOP feature is enabled (B130 = 01), the actual deceleration is sometimes longer than the value set by parameters F003/F203.

The over-voltage LADSTOP feature does not operate by maintaining a constant DC bus voltage. So it is still possible to have an over-voltage trip event during extreme deceleration.

If B131 is set lower than the normal DC bus voltage (when not in decel) by mistake, or if the inverter’s input voltage increases enough, then the inverter will apply LADSTOP (if enabled) all the time. In this case, the inverter can accelerate and run the motor, but it cannot decelerate. If you are not sure that B131 > DC bus voltage, measure the DC bus voltage in your installation and verify that the B131 value is higher.

 

 

“B” Function

Run

 

Defaults

Func.

Name /

 

Description

Mode

-FE

 

-FU

Units

Code

SRW Display

Edit

(EU)

 

(USA)

B130

Over-voltage LADSTOP

Pauses deceleration ramp when DC bus

 

00

 

00

 

enable

 

voltage rises above threshold level, in

 

 

 

 

 

 

 

 

order to avoid over-voltage trip.

 

 

 

 

 

 

 

 

00Disable

 

 

 

 

 

 

OVLADSTOP

OFF

01Enable

 

 

 

 

 

B131

Over-voltage LADSTOP

Sets the threshold level for over-voltage

9

380/

 

380/

V

 

level

 

LADSTOP. When the DC bus voltage is

 

760

 

760

 

 

 

 

above the threshold value, the inverter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

stops deceleration until the DC bus

 

 

 

 

 

 

 

 

voltage is less than the threshold

 

 

 

 

 

 

 

 

setting again. Two voltage ranges with

 

 

 

 

 

 

 

 

1V resolution:

 

 

 

 

 

 

 

 

330 to 395V (200V class)

 

 

 

 

 

 

LADST LVL 0

0380V

660 to 790V (400V class)

 

 

 

 

 