Hitachi X200 Series instruction manual Frequency source Five options select codes

Models: X200 Series

1 286
Download 286 pages 46.11 Kb
Page 252
Image 252

B25

The following table lists the holding registers for the “A” Group Standard Functions.

List of Holding Registers

 

Func.

Name

R/W

Description

 

Network Data

 

 

Code

Reg.

 

Range

Res.

 

 

 

 

 

 

 

 

A001

Frequency source

R/W

Five options; select codes:

1019h

 

0 to 3, 10

 

 

 

setting

 

00...Keypad potentiometer

 

 

 

 

 

 

 

 

 

01...Control terminal

 

 

 

 

 

 

 

 

 

02...Function F001 setting

 

 

 

 

 

 

 

 

 

03...ModBus network input

 

 

 

 

 

 

 

 

 

10...Calculate function output

 

 

 

 

 

 

A002

Run command source

R/W

Three options; select codes:

101Ah

 

1, 2, 3

 

 

 

setting

 

01...Control terminal

 

 

 

 

 

 

 

 

 

02...Run key on keypad, or

 

 

 

 

 

 

 

 

 

digital operator

 

 

 

 

 

 

 

 

 

03...ModBus network input

 

 

 

 

 

 

A003

Base frequency setting

R/W

Settable from 30 Hz to the

101Bh

 

30 to max.

1 Hz

 

 

 

 

 

maximum frequency

 

 

freq.

 

 

 

A203

Base frequency setting,

R/W

Settable from 30 Hz to the 2nd

150Ch

 

30 to max.

1 Hz

 

 

 

2nd motor

 

maximum frequency

 

 

freq.2

 

 

 

A004

Maximum frequency

R/W

Settable from the base frequency

101Ch

 

30 to 400

1 Hz

 

 

 

setting

 

up to 400 Hz

 

 

 

 

 

 

A204

Maximum frequency

R/W

Settable from the 2nd base

150Dh

 

30 to 400

1 Hz

 

 

 

setting, 2nd motor

 

frequency up to 400 Hz

 

 

 

 

 

 

A005

[AT] selection

R/W

Five options, select codes:

101Dh

 

0, 2, 3,

 

 

 

 

 

00... Select between [O] and [OI]

 

 

4, 5

 

 

 

 

 

 

at [AT]

 

 

 

 

 

 

 

 

 

02... Select between [O] and

 

 

 

 

 

 

 

 

 

keypad potentiometer

 

 

 

 

 

 

 

 

 

03... Select between [OI] and

 

 

 

 

 

 

 

 

 

keypad potentiometer

 

 

 

 

 

 

 

 

 

04... Only [O] input active

 

 

 

 

 

 

 

 

 

05... Only [OI] input active

 

 

 

 

 

 

A011

O–L input active range

R/W

The output frequency

1020h

 

0 to 4000

0.1 Hz

 

 

 

start frequency

 

corresponding to the analog

 

 

 

 

 

 

 

 

 

input range starting point,

 

 

 

 

 

 

 

 

 

Range is 0.0 to 400.0

 

 

 

 

 

 

A012

O–L input active range

R/W

The output frequency

1022h

 

0 to 4000

0.1 Hz

 

 

 

end frequency

 

corresponding to the analog

 

 

 

 

 

 

 

 

 

input range ending point, range

 

 

 

 

 

 

 

 

 

is 0.0 to 400.0

 

 

 

 

 

 

A013

O–L input active range

R/W

The starting point (offset) for the

1023h

 

0 to 100

1 %

 

 

 

start voltage

 

active analog input range, range

 

 

 

 

 

 

 

 

 

is 0. to 100

 

 

 

 

 

 

A014

O–L input active range

R/W

The ending point (offset) for the

1024h

 

0 to 100

1 %

 

 

 

end voltage

 

active analog input range, range

 

 

 

 

 

 

 

 

 

is 0. to 100.

 

 

 

 

 

 

A015

O–L input start

R/W

Two options; select codes:

1025h

 

0, 1

 

 

 

frequency enable

 

00...Use offset (A011 value)

 

 

 

 

 

 

 

 

 

01...Use 0 Hz

 

 

 

 

 

 

A016

External frequency

R/W

Range n = 1 to 16, where n =

1026h

 

1 to 17

1 sample

 

 

 

filter time constant

 

number of samples for average.

 

 

 

 

 

 

 

 

 

Set 17 to use 16-samples for avg.,

 

 

 

 

 

 

 

 

 

plus deadband +0.1/-0.2Hz

 

 

 

 

 

Appendix B

Page 252
Image 252
Hitachi X200 Series instruction manual Frequency source Five options select codes